Installation and operating instructions Wilo-Yonos MAXO-Z

11

5.7.3

Insulating

Drinking water applications with fluid temperature

> 20 °C

Fig. 13: 

Insulate, free up condensation drain

1.

Mount thermal insulation shell (accessories) onto pump

housing.

Cold water applications

1.

Use standard, diffusion-proof insulation materials. Empty

condensation drain.

6

Connect

6.1

Personnel requisition

▪ Electrical work must be carried out by an authorised

electrician (in accordance with EN 50110-1).

6.2

Requirements

CAUTION
Incorrect connection

Wrong connection of the pump leads to damage to

the electronics.

▪ Observe voltage rating on the rating plate.

▪ Maximum back-up fuse: 10 A, slow-blow or circuit

breaker with C characteristic.

▪ Never connect to an uninterruptible power supply or

IT-networks.

▪ During external connection of the pump deactivate a

pulse of the voltage (for example phase angle control).

▪ Switching the pump via triacs/solid-state relays must

be examined on a case-by-case basis.

▪ During deactivation with on-site power relay: Rated

current ≥ 10 A, rated voltage 250 V AC

▪ Note switching frequency:

– Switching on/off mains voltage ≤ 100/24 h

– ≤ 20/h at a switching frequency of 1 min between

switching on/off via mains voltage

▪ Secure pump with a residual-current device (type A or

B).

▪ Leakage current I

eff

 ≤ 3.5 mA

▪ The electrical connection must be made via a fixed

connecting cable equipped with a connector device or

an all-pole switch with a contact opening width of at

least 3 mm (VDE 0700/Part 1).

▪ To protect against leakage and for strain relief to the

threaded cable connection use a connection pipe with

sufficient outer diameter.

▪ Lay the connection pipe in such a way that it touches

neither the pipes nor the pump.

6.3

Connection options

Fig. 14: 

Connection options

The pump can be connected to networks with the fol-

lowing voltage ratings:

▪ 1~ 230 V

Summary of Contents for Yonos MAXO-Z

Page 1: ...Pioneering for You Wilo Yonos MAXO Z 2189869 Ed 01 2017 03 en Installation and operating instructions...

Page 2: ...delivery 6 4 2 Accessories 6 4 3 Transport inspection 6 4 4 Transport and storage conditions 6 4 5 Transport 7 5 Installation 7 5 1 Personnel requisition 7 5 2 Safety during installation 7 5 3 Prepari...

Page 3: ...ions Wilo Yonos MAXO Z 3 8 2 Safety during troubleshooting 14 8 3 Error table 15 8 4 Fault signals 15 8 5 Warning signals 15 9 Spare parts 16 10 Disposal 16 10 1 Information on the collection of used...

Page 4: ...ful information on handling the product Symbols These instructions use the following symbols General danger symbol Danger of electric voltage Warning of hot surfaces Warning of magnetic fields Notes 1...

Page 5: ...For further instructions see rating plate and catalogue 2 5 Min inlet pressure Nominal dia meter Fluid temperature 0 to 50 C up to 95 C up to 110 C RP 1 0 3 bar 1 0 bar 1 6 bar RP 1 0 3 bar 1 0 bar 1...

Page 6: ...owed to play with the device Cleaning and user maintenance is not allowed to be carried out by children without supervision 3 4 Safety instructions Electrical current DANGER Electric shock The pump is...

Page 7: ...crews observe the following 1 Close shut off device or drain unit 2 Cool down the unit completely 5 3 Preparing the installation 1 Complete all welding and brazing tasks 2 Flush unit 3 Provide shut of...

Page 8: ...65 Screw diameter M 12 M 12 M 12 M 12 Strength class 4 6 4 6 4 6 4 6 Tightening torque 40 Nm 40 Nm 40 Nm 40 Nm Screw length 55 mm 55 m m 60 m m 60 mm Flange end pump PN 10 DN 32 DN 40 DN 50 DN 65 Scre...

Page 9: ...ing must point in the direction of flow Fig 8 Pump installation 3 Screw together flange with suitable screws and the supplied washers Observe aforementioned tightening torques Fig 9 Opening shut off d...

Page 10: ...the pump Fig 11 Pump installation 3 Insert the supplied flat gaskets into the pump 4 Screw together the pump with the union nuts In do ing so hold it exclusively against the flat faces on the pump hou...

Page 11: ...ump deactivate a pulse of the voltage for example phase angle control Switching the pump via triacs solid state relays must be examined on a case by case basis During deactivation with on site power r...

Page 12: ...ve fault signal line are led together through a 5 wire cable Do not connect SSM pipe to protective low voltage Use 5 x 1 5 mm cable Connection minimum permitted 12 V DC 10 mA maximum permitted 250 V A...

Page 13: ...ts 6 Flip open the plug Fig 18 Connect 7 Remove the elastic fastener from the cable ducts using a small screwdriver 8 Guide the pipes through the cable ducts to the connection sockets Fig 19 Connect 9...

Page 14: ...ressure setpoint H Recommended for systems with balancing valves 7 4 Adjust operating mode and pump output Factory setting The pumps are delivered in control mode p c The re quired delivery head is pr...

Page 15: ...return valve if necessary E10 Blocking Rotor blocked Contact cus tomer service E212 Overload Slow motor Contact cus tomer service E23 Short circuit Motor current too high Contact cus tomer service No...

Page 16: ...ar on the product the packaging or the accompanying documentation It means that the electrical and electronic products in question must not be dis posed of along with domestic waste To ensure proper h...

Page 17: ...0335 2 51 et aux l gislations nationales les transposant EU EG KONFORMIT TSERKL RUNG EU EC DECLARATION OF CONFORMITY DECLARATION DE CONFORMITE UE CE Als Hersteller erkl ren wir unter unserer alleinige...

Page 18: ...kuutuksessa kuvatut tuotteet ovat seuraavien eurooppalaisten direktiivien m r ysten sek niihin sovellettavien kansallisten lakiasetusten mukaisia WILO SE ndearbha onn an cur s os ar na t irg at i r it...

Page 19: ...2014 30 WE Produkt w zwi zanych z energi 2009 125 WE WILO SE WILO SE estne prehlasuje e v robky ktor s predmetom tejto deklar cie s v s lade s po iadavkami nasleduj cich eur pskych direkt v a odpoveda...

Page 20: ...HJUDWH 0 7 ZLOR LWDOLD ZLOR LW D DNKVWDQ 2 HQWUDO VLD OPDW 7 LQIR ZLOR N RUHD 2 3XPSV WG DQJVHR XVDQ 7 ZLOR ZLOR FR NU DWYLD 2 DOWLF 6 5LJD 7 LQIR ZLOR OY HEDQRQ 2 121 6 5 GHLGHK HEDQRQ 7 LQIR ZLOR FR...

Page 21: ...Pioneering for You WILO SE Nortkirchenstr 100 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: