Installation and operating instructions Wilo-Control MS-L 1x4kW
29
TRANSPORT AND STORAGE English
3.4.3. Switchgear
Mains connection:
1~230 V or 3~400 V
Frequency:
50/60 Hz
Max. current:
12 A
Power consumption:
Contactor taut: 15 VA
Downtime status: 8 VA
Max. switching capacity P
2
:
4 kW, AC3
Max. fuse protection on
mains side:
16 A
Activation type:
Direct start-up
Ambient/operating temper-
ature:
-30 to +60 °C
Storage temperature:
-30 to +60 °C
Max. relative humidity:
50 %
Protection class:
IP 54
Control voltage:
24 VDC
Alarm contact switching
capacity:
max. 250 V~, 1 A
Housing material:
Polycarbonate, UV-resistant
Housing dimensions (Wx
-
HxD):
191x240x107 mm
Electrical safety:
Degree of contamination II
3.5. Type key
Example: Wilo-Control MS-L 1x4kW-M-DOL-S
MS
Micro Control switchgear for fixed speed pumps
L
Level-dependent control of the pump
1x
Max. number of pumps that can be connected
4kW
Max. permissible rated power (P
2
) of pump
M
Mains connection:
None = Choice of 1~230 V or 3~400 V
M = alternating current (1~230 V)
T4 = three-phase current (3~ 400 V)
DOL
Direct-on-line starting of pump
S
Version of switchgear:
Without = standard version with main switch
S = Version for lifting units without main switch,
with cable and plug
O = Version without main switch and without
plug
3.6. Options
By inserting a rechargeable battery (available
as an accessory) alarm signals can be emitted
independent of the electricity network in case of
a fault. An audible constant tone will be emitted
as an alarm.
3.7. Scope of delivery
Standard variant and "O" variant
• Switchgear
•
2x reducing seals for threaded cable connection
•
2x assembled jumper wires for mains connection
• Installation and operating instructions
Variant "S"
•
Switchgear with connected cable and plug:
•
1~230 V: Shockproof plug
•
3~400 V: CEE phase inverter plug with phase
inverter
• Installation and operating instructions
3.8. Accessories
• Float switch WA for wastewater and sewage free
of faeces
• Float switch MS1 for abrasive sewage containing
faeces
•
NiMH rechargeable battery (9 V/200 mAh) for
alarm signals to indicate a power failure
•
Horn 230 V, 50 Hz
•
Flash light 230 V, 50 Hz
•
Signal lamp 230 V, 50 Hz
Accessories have to be ordered separately.
4. Transport and storage
4.1. Delivery
On delivery, check immediately that the ship-
ment is complete and undamaged. If any parts
are damaged or missing, the transport company
or the manufacturer must be notified on the day
of delivery. Claims made after this date cannot be
recognised. Damage to parts must be noted on
the freight documentation.
4.2. Transport
Only the packaging used by the manufacturer or
supplier may be used for transport. This normally
precludes the possibility of damage occurring
during transport and storage. The packaging
should be stored in a safe place for reuse if the
product is frequently used at different locations.
4.3. Storage
On delivery, switchgears may be placed into tem-
porary storage for up to 1 year until use providing
the details below are observed.
The following should be taken into consideration
for storage:
•
Place the packaged switchgear on a firm subsur
-
face.
•
Our switchgears may be stored at -10 °C to
+60 °C at a max. relative humidity of 50 %.
The store room must be dry. We recommend
a frost-protected room for storage with a tem
-
perature between 10 °C and 25 °C and a relative
air humidity of 40 % to 50 %.
Avoid formation of condensate!
• Seal the threaded cable connections securely to
prevent ingress of moisture.
• Connected power supply cables and attached
plugs should be protected from kinking, damage,
and moisture.