English
Installation and operating instructions Wilo-SiClean Comfort
43
5.1.2.1
Select baud rate
9.6
19.2
38.4
76.8
[kBaud]
19.2
5.1.2.2
Adjustment, slave address
1 … 128 … 255
128
5.1.2.3
Select parity
even
none
odd
even
5.1.2.4
Select number of stop bits
1
2
1
5.1.2.5
Adjustment, BACnet device
Instance ID
0 … 128 … 9999
128
5.5.0.0
Menu output setting
–
–
5.5.1.0
Common run message
Selection of operating SBM relay:
Run – minimum one pump is running
Ready – System is on
Ready
Run
Run
5.5.2.0
Common fault message
Selection of operating SSM relay:
Raise – relay on in case of error
Fall – relay off in case of error
Fall
Raise
Raise
6.0.0.0
Menu error messages
–
–
Menu no./
notes
Display
Description
Parameter range
Factory setting
Summary of Contents for SiClean Comfort 12
Page 2: ...Fig 1 1 10 11 5 6 4B 4A 3 2 8 9 7 Fig 2 5 4 1 2 3...
Page 3: ...Fig 3 3 6 2 4 5 1 1...
Page 4: ...Fig 4...