39
Installation and operating instructions – Wilo-Helix VE / MVIE 11/15/18,5/22kW – IE5
English
10.1
Faults table
All incidents mentioned hereafter will have the
following effect:
•
Deactivation of the SBM relay (when parameter
-
ised in “available transfer” mode).
•
Activation of the SSM relay “failure transfer”
when the max. quantity of one malfunction type
is reached within a 24-hour
period.
• Lighting of a red LED
.
Error
code
Ramp time
before
signalling of
error
Time
before the
error
is taken into
account after
signalling
Waiting time
before
automatic
reactivation
Max.
error in
24 h
Faults
Possible causes
Remedies
Waiting
time
before
reset
E001
60 s
0 s
60 s
6
The pump is overloaded,
malfunctioning
Density and/or viscosity of the
pumped fluid too high
300 s
The pump is obstructed
by foreign bodies
Dismantle the pump,
replace the malfunctioning
components or clean it
E004
(E032) ~5s
0 s
300 s
6
The power supply to
the converter is in
undervoltage
Check the voltage at the
converter terminals
300 s
E005
(E033) ~5s
300
s
0 s if error
deleted
6
The power supply to the
converter is at overvoltage
Check the voltage at the
converter terminals
0 s
E006
~5s
300
s
0 s if error
deleted
6
A power supply phase is
missing
Check the power supply
0 s
E007
0 s
0 s
0 s if error
deleted
Unlimited
The converter operates as
a generator. Warning, no
pump deactivation
The pump has switched
direction, check the
impermeability of the valve
0 s
E010
~5s
0 s
Unlimited
1
The pump is blocked
Dismantle pump, clean it
and replace the faulty parts.
Possible mechanical motor
malfunction (roller bearings)
60 s
E011
15s
0 s
60 s
6
The pump is deactivated
or is running dry
Re-prime by filling the
pump (See §
9.3). Check the
impermeability of the foot
valve
300 s
E020
~5s
0 s
300 s
6
The motor is heating up
Clean the cooling ribs at the
back and under the converter,
as well as the fan cap
300 s
Room temperature above
product characteristics
Improve the ventilation of the
premises
E023
0 s
0 s
60 s
6
The motor is short-
circuited
Remove the motor-converter
from the pump and check it or
replace it
60 s
E025
0 s
0 s
Unlimited
1
A phase of the motor is
missing
Check the connection
between the motor and the
converter
60 s
E026
~5s
0 s
300 s
6
The motor’s temperature
sensor is faulty or has a
bad connection
Remove the motor-converter
from the pump and check it or
replace it
300 s
E030
E031
~5s
0 s
300 s
6
The converter is heating
up
Clean the cooling ribs at the
back and under the converter,
as well as the fan cap
300 s
Room temperature above
product characteristics
Improve the ventilation of the
premises
E042
~5s
0 s
Unlimited
1
The sensor cable (IN1)
is cut
Check for the correct power
supply and wiring to the
sensor
60 s
E050
60 s
0 s
0 s if error
deleted
Unlimited
The BMS communication
is faulty
Check the connection
300 s
E077
0 s
0 s
Unlimited
1
24 V power supply voltage
of sensors faulty
Check the sensors and their
connections
60 s
E---
0 s
0 s
Unlimited
1
Converter internal
malfunction
Call customer service
60 s
Summary of Contents for Helix VE 11kW-IE5
Page 2: ...Fig 1 ...
Page 3: ...Fig 2 HELIX VE 10 16 ...
Page 4: ...Fig 2 HELIX VE 22 36 52 ...
Page 8: ...Fig 9 HELIX VE 22 36 52 Fig 8 x2 x4 ...
Page 9: ...Fig A1 1 1 ...
Page 10: ...2 2 4 4 3 3 Fig 2D Fig 3D 4 4 3 3 2 2 Fig 4D 3 3 4 4 2 2 ...
Page 11: ...en Installation and operating instructions 12 ...
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......