CONNECTION TO MAINS SUPPLY
POWER TERMINALS
–
Connect the cable 4 wires
wires
≥
ø4 mm2
No special order
(3 earth)
of the phases
CONNECTION OF INPUTS/OUTPUTS
TERMINAL FOR INPUTS/OUTPUTS (1 to 10)
– Control of the converter by an external
(see fig. 6)
(See chapter 6 :
starting up
)
system with a signal (0-10V) or 0-20mA)
A removable jumper has to be placed
according to the type of signal.
- Control with a current signal ............................
0-20mA
put the bridge in low position.
- Control with a voltage signal ...........................
0-10V
by default the bridge is in high position,
if not carry out the change.
- Possibility to have a remote control ................
Accessories
(free contact).
ex :
Float switch, pressure gauge for dry-running...
CONNECTION OF THE SERIES CONTACTS
TERMINAL FOR SERIES CONTACTS
The speed variator is fitted with an output relay with
free contact aimed for an interface to centralized control
For example : control box, pumps control…
«Available transfer» relay :
See fig.6
Bornes : 41 - 42 - 43
Example : 6 defects with a variable time limit on 10 sliding
- feature of the contact .....................................
min12V/10mA
minutes according to the following scale :
The relay is actived when the pump runs or
max250V/1A
is in a position to run.
When a first defect appears or by mains supply
active relay
cutoff (the pump stops), the relay is no more
active. Information are given to the control box,
regarding the availability of the pump permanently.
rest relay
The number of defects is stored thanks to a
counter.
If the number of defects is lower than 6 and if
after 10 sliding minutes no new defect has been
detected, so the number of defects of the
counter is reduced of 1.
The pump is permanently stopped the counter
count 6 defects. An impulse on the RESET
button initialize the counter.
ENGLISH
17
Details of electrical connections
– Loosen the screws and remove the converter cover.
L1
L2
L3
PE
zero volt
current input 0-20mA
removable bridge
7
6
5
4
3
2
1
G
N
D
0-
20
M
A
zero volt
voltage input 0-10V
removable bridge
7
6
5
4
3
2
1
G
N
D
0-
10
V
18
17
16
15
14
12
11
Remote control
1
2
3
4
5
6
10 sliding minutes
“
av
ai
la
b
le
tr
an
sf
er
”
D
ef
ec
t
ap
p
ea
ra
nc
e
Final
Stop