10 Faults, causes and remedies

DANGER! Risk of death!
Only a specialised and qualified personnel is authorized to repair!
Observe the safety instructions (see chapter 9).

 

Fault

ElectronicControl behaviour

Remedies

E011
DRY RUN

The ElectronicControl starts 
the pump every 30 minutes 
over 24 hours. If dry running 
remains, it switches off the 
pump.

Check the hydraulic supply.

If a set point pressure higher 
than the pressure the pump 
can deliver is programmed, 
the ElectronicControl will 
consider it as dry running. 

E021
OVERLOAD

After the alarm detection the 
ElectronicControl will try 4 
times to start the pump. After 
these 4 trials the pump is swit-
ched off.

Check that the rotor is not 
locked. 
Check the input data in the 
ElectronicControl. 
Check the state of the fuses..

E025
DISCONNECT MOTOR

Motor supply stop

Check the motor winding. 
Check the supply cables.
Check the state of the 20A 
fuses (Fig. 4, Pos. 4).

E040
P SENSOR DEFFECT

The ElectronicControl stops.Q

Contact the technical service 
department:

E031
OVER T°

If the temperature is too high, 
the ElectronicControl stops 
and then the pump. 

Check that the water tempe-
rature does not exceed 40°C.
Check that the ambient tem-
perature does not exceed 
50°C.

E023
SHT CIRCUIT

After the alarm detection the 
ElectronicControl will try 4 
times to start the pump. After 
these 4 trials the pump is swit-
ched off.

Check the motor. 
If the problem remains, con-
tact the manufacturer. 

E071
EEPROM

If the ElectronicControl 
detects a defect on its internal 
memory this error will be dis-
played.

Contact the technical service 
department:

E005
HIGH VOLTAGE

If the ElectronicControl 
detects an overvoltage, it 
stops over some seconds and 
then starts again. 

Check the ElectronicControl 
supply voltage. 

1_Wilo-ElectronicControl.book  Seite 27  Montag, 11. Juli 2011  3:14 15

Summary of Contents for Electronic Control MM6

Page 1: ...de montage et de mise en service NL Inbouw en bedieningsvoorschriften E Instrucciones de instalaci n y funcionamiento I Istruzioni di montaggio uso e manutenzione GR RUS Wilo ElectronicControl 4 159 7...

Page 2: ...Fig 1 Fig 2 1_Wilo ElectronicControl book Seite 2 Montag 11 Juli 2011 3 14 15...

Page 3: ...Fig 3 Fig 4 1_Wilo ElectronicControl book Seite 3 Montag 11 Juli 2011 3 14 15...

Page 4: ...Fig 5 Fig 6 Fig 7 1_Wilo ElectronicControl book Seite 4 Montag 11 Juli 2011 3 14 15...

Page 5: ...f the EC declaration of conformity is a component of this installation and operating instruction If the ranges mentioned in this instruction are subject to changes without any prior approval this decl...

Page 6: ...ects Property damage 2 4 Safety instructions for the operator The existing directives for accident prevention must be adhered to Danger from electrical current must be eliminated Local directives or g...

Page 7: ...d those specified in the catalogue or data sheet 3 Transport and storage The product is delivered in a cardboard box It is protected against moisture and dust As soon as the product arrives immediatel...

Page 8: ...f the ElectronicControl 1 230V T Electrical supply of the motor T 3 230V M 1 230V 6 Maximal current delivered in A 5 2 Technical data Maximum operating pressure 15 bar Setting range 0 5 up to 12 bars...

Page 9: ...03 Cable gland of the dry running protection 04 Cable gland of the serial communication as option 05 Suction 06 Discharge 07 User interface Pos Description of the components 01 Pump 02 ElectronicContr...

Page 10: ...10 2 dry running over currents too high water temperatures frost short circuits over voltages Under voltages In case of defect such as dry running overvoltage the led blinks and the ElectronicControl...

Page 11: ...the next parameter is displayed on the screen With the push button you exit SETTINGS no saving of the last change or HISTORIC menu and go back to STANDARD display mode or SERVICE NOTE The data are sav...

Page 12: ...essure set ting in the installation START DELTA P 0 3 BAR Start delta P Define the starting pressure as starting pressure setpoint pressure start delta P TIME BEFORE STOP 5 S TIME BEFORE STOP Time set...

Page 13: ...one by a qualified electrician and in compliance with the regulations in force Follow all accident prevention regulations Before installation and electrical connection switch off the product station s...

Page 14: ...tronicControl A blad der tank over 2 liter volume Fig 2 Pos 4 shall allow an optimal regulation of the pressure inside the installation A pre setting pressure 0 5 bars lower than the set point pressur...

Page 15: ...pump at suction the priming of the pump shall be done manually manual mode During the priming step see operating instruction of the pump it may drive the pump at its maximum speed As soon as the pump...

Page 16: ...T MOTOR Motor supply stop Check the motor winding Check the supply cables Check the state of the 20A fuses Fig 4 Pos 4 E040 P SENSOR DEFFECT The ElectronicControl stops Q Contact the technical service...

Page 17: ...To avoid queries and order errors please supply all data on the name plate with every order Subject to change without prior notice E004 LOW VOLTAGE If the ElectronicControl detects an under voltage i...

Reviews: