English
23
WILO SE 05/2011
ROTATION SENSE
0
Hz
ROTATION
SENSE
Setting of the rotation
sense. See the pump
identification plate.
Push on
to start
the pump (at 30hz)
and check the rotation
sense.
MIN SPEED
30
HZ
MIN SPEED
Define the minimum
motor rotation speed
DRY RUN PROT
NO
DRY RUN PROT
If the installation is
provided with a level
switch (flow switch or
other ones) change NO
by YES.
PRESSURE SETTING
2,0
BAR
PRESSURE
SETTING
Working pressure set-
ting in the installation
START DELTA P
0,3
BAR
Start delta P
Define the starting
pressure as : starting
pressure = setpoint
pressure - start delta
P.
TIME BEFORE STOP
5
S
TIME BEFORE
STOP
Time setting before
pump stop when there
is no flow.
DISPLAY
STANDARD
DISPLAY
Define the display
mode :
• STANDARD:network
pressure (bar) +
pressure setting
(bar)
• SERVICE : rotation
frequency (Hz) +
pressure setting
(bar) + networkpres-
sure (bar) + flow
switch detection (1
or 0)
HISTORIC
RUNNING TIME
HOURS
26H
RUNNING TIME
Total pump running
hours (H).
Display
Menu level 1
Menu level 2
Description