English
Installation and operating instructions Wilo-DrainLift XXL
7
DrainLift XXL ...
880-2/1.7 880-2/2.1 1080-2/3.9
1080-2/5.2
1080-2/7.0
1080-2/8.4
Connection voltage
[V]
3~400 ± 10 %
Connection version
Switchgear with main switch
Power consumption P
1
[kW]
2 x 2.3
2 x 2.7
2 x 4.4
2 x 6.2
2 x 8.4
2 x 10.0
Nominal current
[A]
2 x 6.7
2 x 7.1
2 x 10.5
2 x 12.8
2 x 15.6
2 x 18.1
Mains frequency
[Hz]
50
Protection class
Unit: IP 67 (2 mwc, 7 days)
Switchgear: IP 54
Speed
[rpm]
1450
Start-up type
Direct
Star-delta
Operating mode
(with regard to the pump)
S1; S3 25 % 60 sec
Max. switching frequency
[1/h]
120 (60 per pump)
Max. total delivery head
[mwc]
8.5
10.5
12
15.5
18.5
21
Max. permitted geodesic delivery
head
[mwc]
6.5
8.5
9.5
12
15
17.5
Max. permissible pressure in the
pressure pipe
[bar]
3
Max. volume flow
*
1)
[m³/h]
75
85
140
140
140
140
Min. volume flow
*
1)
[m³/h]
19
20
36
38
44
47
Max. fluid temperature
[°C]
40 (briefly 3 min, 60°C)
Min. fluid temperature
[°C]
3
Max. ambient temperature
[°C]
40
Max. solid grain size
[mm]
80
95
Sound-pressure level (depending
on the duty point)
*
2)
[dB(A)]
< 70
Gross volume
[l]
800
Recommended level
Switching point, pump 1 ON
*
3)
[mm]
560
Minimum value of level
Switching point, pump 1 ON
*
3)
[mm]
500
550
Minimum value of level
Switching point, pump OFF
*
3)
[mm]
140
160
Switching volume (pump 1 only;
with recommended switching
level ON and minimum switching
level OFF)
[l]
460
440
Max. permissible inlet quantity in
one hour (switching operation,
switching volume with recom-
mended switching level)
*
4)
[l]
25% of volume flow value at duty point
Dimensions (W/D/H)
[mm]
1965/1695/880
1990/1710/880
Net weight
(complete, without packaging)
[kg]
195
230
Pressure connection
[DN]
80
100
Inlet connections
[DN]
100, 150
Ventilation connection
[DN]
70
*
1)
Observe the permissible flow rate in the pressure pipe: 0.7 to 2.3 m/s according to EN 12056
*
2)
Improper unit and pipe installation, as well as impermissible operation, can increase the acoustic emissions.
*
3)
Measured in relation to installation level
*
4)
The current peak flow must always be lower than the volume flow of a pump at the duty point