Faults, causes and remedies
en
Installation and operating instructions Wilo-Control EC/ECe-Booster
81
Main menu
1
5
3
2
Fig. 66:
Acknowledge fault
‡
All faults rectified.
1. Press the operating button for 3 s.
⇒ Menu 1.00 appears.
2. Turn the operating button until menu 6 appears.
3. Press the operating button.
⇒ Menu 6.01 appears.
4. Press the operating button.
5. Change the value to “reset”: Turn the operating button.
6. Press the operating button.
▶ The fault indication is reset.
Easy Actions menu
‡
All faults rectified.
1. Starting the Easy Actions menu: Turn the operating button 180°.
2. Select menu item “Err reset”.
3. Press the operating button.
▶ The fault indication is reset.
Fault acknowledgement failed
If there are further faults, the faults are displayed as follows:
▪ The fault LED lights up.
▪ The error code of the last fault is shown in the display.
All other faults can be called up from the fault memory.
If all faults have been rectified, acknowledge the faults again.
11.4
Fault memory
The switchgear stores the last ten faults in the fault memory. The fault memory works
according to the first in/first out principle. The faults are displayed in descending order
in the menu items 6.02 to 6.11:
▪ 6.02: the last/latest fault
▪ 6.11: the oldest fault
11.5
Error codes
Code*
Faults
Causes
Remedies
E006
Rotating field error
Mains connection faulty, incorrect
rotating field
Establish a clockwise rotating field at the mains
connection.
In case of an alternating current
connection, deactivate rotating field monit-
oring!
E040
Pressure sensor fault
No connection to the sensor
Check the connection cable and sensor. Re-
place the defective component.
E062
Low water/dry-running protection
Low water in the break tank
Check the inlet and system parameters.
Check that the float switch is working correctly.
Replace the defective component.
E080.x
Control EC-Booster: Pump fault**
Bimetallic strip or motor current
monitoring has been tripped.
Check functionality of pump.
Check that the motor has sufficient cooling.
Check the set rated current.
Check connection cable
Contact customer service.
E080.x
Control ECe-Booster: Frequency
converter fault**
Frequency converter has indicated a
fault.
Read off the fault on the frequency converter
and resolve in accordance with instructions.
Key:
*
“x”
= display the pump to which the fault shown applies!
** Fault must be
manually
acknowledged.
11.6
Further steps for troubleshooting
If the points listed here do not rectify the fault, please contact customer service. Costs
may be incurred if other services are used. For more details, please contact customer
service.
Summary of Contents for Control EC-Booster
Page 2: ......
Page 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Page 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Page 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Page 1208: ......
Page 1209: ......
Page 1210: ......