et
Lisa
304
WILO SE 2019-07
Holding register
(Protocol)
Name
Data type
Scale & unit
Elements
Access*
Added
8. EC
9. ECe
10. ECe NWB
40014
(13)
Bus command timer
ENUM
0. -
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW
31.000
40015
(14)
Drives on/off
BOOL
RW
31.000
40025
(24)
Control mode
ENUM
0. p-c
1. dp-c
2. dp-v
3. dT-c
4. dT-v
5. n(TV)
6. n(TR)
7. n(TP)
8. n(TA)
9. n-c
10. fill
11. empty/drain
12. FTS
13. cleans/day
14. cleans/
month
R
31.000
40026
(25)
Current value
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
R
31.000
40041
(40)
Pump 1 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40042
(41)
Pump 2 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40043
(42)
Pump 3 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40062
(61)
Switch box state
BITMAP
0: SBM
1: SSM
R
31.000
40139 - 40140
(138-139)
Error state
BITMAP32
0: Sensor error
1: P max
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6
Alarm
11: -
12: -
13: Frost
14: Battery Low
R
31.000
Summary of Contents for Control EC-Booster
Page 2: ......
Page 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Page 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Page 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Page 1208: ......
Page 1209: ......
Page 1210: ......