1 pump is not turning
Thermal relay activated
The “Fault” indicator light for the pumps must be
illuminated on the switchgear. Check the current
setting.
Magnetic circuit breaking
activated
Reset.
If the activations persist, check the current absorbed
by the motor in question. If this current is a lot higher
than that indicated on the motor, this is defective and
shall have to be changed.
Pump shaft blocked
Switch off the power supply for the switchgear,
then check that the shaft is turning freely. If this
is blocked, dismantle the pump.
Winding malfunction
Disconnect the terminal for the motor in question
and check the power supply at the terminals and the
stator’s insulation. Replace the motor if necessary.
Contactor coil burnt
Change it.
No pressure on the discharge side
Selected flow rate higher than
the capacity of the pressure-
boosting system
Consider replacing the pressure-boosting system
for another one that is more suitable (contact us in
any case).
1 or 2 pumps deactivated
Check that the suction strainer on the reservoir
does not absorb air and that the filling of the
reservoir is not too close to the strainer.
Municipal water supply pressure
below minimum prescribed
pressure
Contact the local water supplier or replace the
pressure-boosting system. Contact us.
The pumps are turning in the
wrong direction
Cross-wire 2 power supply wires to the motor
terminals.
1 pump is obstructed by
foreign bodies
Dismantle and clean the pump.
The motors are supplied by
insufficient voltage
Check the voltage at the motor terminals.
Faults
Causes
Remedies
Summary of Contents for COE-2 MHIL
Page 2: ...Fig 1 Fig 2 Fig 3...
Page 3: ...Fig 4 Fig 5 Fig 6 Fig 7 Fig 8...
Page 4: ......
Page 43: ...Italiano Istruzioni di montaggio uso e manutenzione Wilo COE 2 MHIL 43...
Page 57: ...Espa ol Instrucciones de instalaci n y funcionamiento Wilo COE 2 MHIL 57...
Page 71: ...Portugu s Manual de instala o e funcionamento Wilo COE 2 MHIL 71...
Page 73: ...Wilo COE 2 MHIL 73 1 2 2 1 2 2 2 3...
Page 74: ...74 WILO SE 02 2020 2 4 2 5 Y IEC VDE 2 6 2 7 2 8 4 3...
Page 80: ...80 WILO SE 02 2020 PR1 1 2 1 MANU 1 2 AUTO 0 3 bar 2 PR2...
Page 81: ...Wilo COE 2 MHIL 81 9 EN 806 5 Fig 1 6 10 Wilo 9...
Page 82: ...82 WILO SE 02 2020 1 2 NPSH 0 NPSH 2...
Page 83: ...Wilo COE 2 MHIL 83 1 1 2 2 1...
Page 84: ...84 WILO SE 02 2020 Wilo 11 Wilo 12 1 2 www wilo com...
Page 85: ...Wilo COE 2 MHIL 85...
Page 87: ...Wilo COE 2 MHIL 87 1 2 2 1 2 2 2 3...
Page 88: ...88 WILO SE 02 2020 2 4 2 5 IEC VDE 2 6 2 7 2 8 4 3...
Page 92: ...92 WILO SE 02 2020 7 3 7 4 7 4 1 5 2 7 4 2 250 2 A Fig 5...
Page 94: ...94 WILO SE 02 2020 1 MANU 1 2 PR2 AUTO 0 3 2 35...
Page 96: ...96 WILO SE 02 2020 1 2 NPSH 0 NPSH 2...
Page 97: ...Wilo COE 2 MHIL 97 1 1 2 2 1...
Page 98: ...98 WILO SE 02 2020 Wilo 11 Wilo 12 1 2 www wilo com...