background image

4

3.2  Transport

The booster must be transported on a pallet and 

film wrapped to protect it against moisture and 

dust. When the product is delivered, check for any 

damage in transit. If any defect is found, inform 

your Wilo agent within 72 hours.
• 

The equipment must be transported by 

means of authorised load devices

• 

Transport straps must be placed around the 

steel base frame

• 

The manifolds will not withstand loads and 

should not be used to secure loads in transit

4  Description and Operation

4.1  Description of Control Device

The automation of the system is ensured by the 

Electronic Control. Electronic Control contains an 

electronic regulation system using pressure and 

flow sensors and a frequency inverter. 3 pump 

sets also use a Speedcentre control panel in 

conjunction with the inverters.

4.2  Operation Modes

4.2.1  Automatic Mode (1 & 2 Pump Only)

You can access this mode by pressing the 

Operating Mode Auto button (Fig 2) on the 

drive - see NOTE below.  In automatic mode the 

Electronic Control maintains a constant pressure 

in the system by varying the speed of the pumps 

to meet the demand. The pressure will be constant 

according to the pre-determined pressure set 

point. The Electronic Control starts the pump 

when the installation pressure (NET P) is lower 

than the set point pressure (P SET) minus the 

pressure gap set (START DELTA P). The Electronic 

Control stops after a time period set (TIME BEFORE 

STOP) when the installation pressure (NET P) has 

reached the set point pressure (P SET) and when 

the flow is zero.

NOTE - AUTO Button only needs to be pressed 

on pump one.  If a second drive is present then 

they will communicate between the two drives. 

The master pump will have a solid green light 

and the slave pump will have a flashing green 

light

4.2.2  Manual Mode (1 & 2 Pump Only)

You can access this mode by holding down the 

Manual Operating button (Fig 2) on the drive. 

The pump starts at maximum frequency. When 

released the pump slows down to a complete stop.

4.2.3  Automatic Mode (3 Pump Only)

All controls and settings on a 3 pump set are 

done via the Speedcentre controller (Fig 3) and 

are communicated to the drives. Settings can 

be entered into the Speedcentre from the main 

screen by pressing the menu button (Fig 3). To 

start automatic mode press the Auto button 

this will do a search for the pumps then initiate 

automatic mode. The Speedcentre starts the 

pump when the installation pressure is lower than 

the set point pressure minus the pressure gap set. 

The Speedcentre stops after a time period set 

when the installation pressure has reached the set 

point pressure and when the flow is zero.

DANGER!  If power is lost during automatic mode 

and pressure in the system drops, on return of 

the power the pumps will run to meet system 

pressure. To avoid hammer effect in the system 

Wilo recommend you install a Wilo Cavsa Valve 

Product Code: 2817747
4.2.4  Manual Mode (3 Pump Only)

You can access this mode by pressing the OK 

button (Fig.2) on the Speedcentre this will do 

a search for the pumps then you will be able to 

select each pump manually. Select a pump by 

pressing ENTER this will run thepump at full speed 

until ENTER is pressed again to stop the pumps.

NOTE – Only one pump at a time can be run in 

manual mode
4.3  Operating Features
4.3.1  Fault Contacts

Terminals for individual pump volt free contacts 

found in the “mains box” (Fig.1). Normally open 

and normally closed contact per pump can be 

used for an external fault signal and are rated at 

230V 1A. The contacts change state if any alarm 

is activated.

NOTE 

– Speed centre also has one set of N/O and 

N/C volt free contacts 230V 1A(3 pump set only

)

4.3.2  Low Water Protection

Terminals for the low water cut out switch can 

be found in the “mains box” (Fig.1). An 18v DC 

input protects the booster against lack of water 

via either a pressure switch or a float switch (not 

supplied) and will activate within 3 seconds of the 

switch operating. This can be turned off from the 

within the drive menu. 

WARNING! Low water protection terminals 

linked out as factory standard. Do not apply 

external voltage to the terminals.

Summary of Contents for 29993227

Page 1: ...V608 29993231 Centrum SV1004 29993232 Centrum SV1006 29993233 Centrum DV406 29993234 Centrum DV408 29993235 Centrum DV605 29993236 Centrum DV608 29993237 Centrum DV1004 29993238 Centrum DV1006 2999323...

Page 2: ...3 1 Fault Contacts 4 4 3 2 Low Water Cut Protection 4 4 3 3 Dry Run Protection 5 4 3 4 Master Slave Function 2 3 pump only 5 5 Installation 5 1 Local 5 5 2 Hydraulic Connections 5 5 3 Electrical Conn...

Page 3: ...entioned 2 2 Risks Incurred by Failure to Comply Failure to comply with the safety precautions could result in personal injury or damage to the pump or installation It could also invalidate any claims...

Page 4: ...ows down to a complete stop 4 2 3 Automatic Mode 3 Pump Only All controls and settings on a 3 pump set are done via the Speedcentre controller Fig 3 and are communicated to the drives Settings can be...

Page 5: ...below Fig 5 The incoming mains connection must comply with local regulations As a protection measure the booster must be earthed according to the regulations i e according to the local regulations an...

Page 6: ...tions The full warranty document is downloadable at www wilo co uk click on local information then downloads Before requesting a site visit the following information must be available to the service t...

Page 7: ...nic Control Drive Fig 3 Speedcentre 3 pump only Manual Mode Inverter On Green LED Automatic Mode Alarm Red LED Menu Pump Running Yellow LED Enter Pump in Automatic Mode Green LED Value Setting Up Valu...

Page 8: ...8 Fig 5 1 Wiring Schematics 1 Pump System Fig 4 Pump Schematics...

Page 9: ...9 Fig 5 2 Wiring Schematics 2 Pump System...

Page 10: ...10 Fig 5 3 Wiring Schematics 3 Pump System...

Page 11: ...running hours Hrs Pump Cycles Total number of pump cycles one cycle one run and stop Power On Number of times the drive has been powered on Max Pressure Maximum pressure of the installation Bar Short...

Page 12: ...OVER T If the temperature is too high the controller will stop the motor from running Check that the water temperature does not exceed 40 C Check that the ambient temperature does not exceed 50 C E02...

Page 13: ...Pumps not primed Check that the suction strainer does not let air in or the tank filling point is too close from the strainer A pump is obstructed by particles Have the pump dismantled and cleaned Vo...

Page 14: ...V406 1 16 E KS 400 50 4193858 HELIX V408 1 16 E KS 400 50 4156034 HELIX V605 1 16 E KS 400 50 4156038 HELIX V608 1 25 E KS 400 50 4150543 HELIX V1004 1 16 E KS 400 50 4150546 HELIX V1006 1 16 E K 400...

Page 15: ...netic Compatibility Directive WEEE Directive ROHS Directive As well as following harmonized standards If the above mentioned series are technically modified without our approval this declaration shall...

Page 16: ...Wilo UK LTD Second Avenue Centrum 100 Burton on Trent Staffordshire DE14 2WJ T 44 0 1283 523000 E sales uk wilo com www wilo com gb en Copyright Wilo UK LTD 2020...

Reviews: