Rev. 12/2018
Installation & Operation Manual
AquaFount-90
®
Washfountain
WAF-2200 Series
Willoughby Industries, Inc.
TOLL FREE
(800) 428-4065
● LOCAL
(317) 875-0830
● FAX
(317) 875-0837
Page 21
www.willoughby-ind.com
INSTALLATION INSTRUCTIONS
Visit our website at http.//www.willoughby-ind.com
2210 West Morris Street • P.O. Box 21217 • Indianapolis, IN 46221
(317) 638-2381 • Fax: (317) 638-6110 • (800) 428-4065
© Rev. 11/2007
Page 15
To Install
Q
NOTE:
Installation should be in accordance with accepted
plumbing practices. Flush all piping thoroughly before installa-
tion.
1. Locate a suitable place for the tempering valve. Valve should
be accessible for service and adjustment and as close to the
point-of-use as possible.
2. Connect hot and cold water to the supply valve using 1/2”
NPT or 3/8” compression connections.
3. Connect outlet of tempering valve to fi xture(s) using 1/2”NPT
or 3/8” compression connections.
4. Turn on hot and cold water supplies. If any leaks are
observed, tighten connections as necessary to stop leaks
before proceeding.
5. Turn on fi xture and allow water to fl ow for 2 minutes.
Measure water temperature at outlet. If water is not at
desired temperature, adjust as necessary.
Specifi cations
Q
e480-00 .......................................................1/2" NPT (Rough Bronze)
e480-01 .................................................... 1/2" NPT (Rough Chrome)
e480-10 ...................................... 3/8"Compression (Rough Bronze)
e480-11 .....................................3/8"Compression (Rough Chrome)
Capacity: ................................................................. 4.0 gpm (15.0 l/m)
Approach Temperature: ..........................5°F (2.8°C) above set pt.
Max. Operating Pressure: ......................................125psi (862 kpa)
Max. Static Pressure: .............................................125psi (862 kpa)
Max. Hot Water Temperature: ....................................180°F (82°C)
Temp. Adjustment Range:
............................................ ASSE Type T/P: 95 – 110°F (43-48°C)
................................................. ASSE Type T: 80 – 120°F (27-49°C)
Minimum Flow: ........................................................ 0.5 gpm (2.2 l/m)
Checks: ......................................................................................Integral
Construction: ........................................................... Cast Brass Body
Certifi ed: ................................................................................CSA B125
Listing .....................................................ASSE 1016-1996 (Type T/P)
.............................................................................................ASSE 1070
To Adjust Temperature
Q
1. Loosen locknut.
2. Turn on fi xture and run water for at least two (2) minutes
to allow supply temperature to stabilize.
3. Turn temperature stem counter-clockwise for hotter or
clockwise for colder outlet temperature.
4. Tighten locknut to prevent accidental or unauthorized
temperature adjustment.
5. Re-check outlet temperature.
Repair Kit
Q
Motor Repair Kit ........................................................................480-270
HydroGuard
®
T/P Series e480
Lavatory Combination Valve
Installation Instructions
IS-P-e480
Figure 1
Figure 2:
Typical Installation
Outlet
Hot Water
Inlet
Temperature
Adjustment
Stem
Locknut
Cold Water
Inlet
Advanced Thermal Activation
© Rev. 5/2010
Adjustable Mixing Valve Installation