background image

 
 

PMP

 

Oil Furnaces

 – 

Furnace Manual

 

22

  

670-000-003/1010 

10

 

Service and maintenance 

(continued)

 

 

Service/maintenance procedures 

To lubricate and inspect blower motor 

DO NOT over-oil motors. Adding too much oil can 
damage the motor bearings, resulting in blower 
motor failure. 

Belt-drive motor: Oil annually, using 3 drops of S.A.E. #10 oil (or 
other if specified by motor manufacturer). Blower bearings are 
permanently lubricated and do not require oiling. Verify that the 
blower, motor pulleys and belt are in good condition. Replace if 
necessary. 

Direct-drive motor: Oil annually using 2 drops of S.A.E. #10 oil (or 
other if specified by motor manufacturer). Oiling is normally not 
required until the beginning of the third year of operation. 

Clean blower wheel – Vacuum dust from blower wheel blades and 
surrounding area. 
 

To clean heat exchanger 

The heat exchanger must be cleaned and inspected 
at least once each year. Operating the furnace with 
a fouled or leaking heat exchanger could result in 
severe personal injury, death or substantial property 
damage. 

The combustion chamber contains ceramic fiber 
materials. Wear a NIOSH-approved respirator while 
cleaning the furnace and follow WARNING on page 
21 for proper handling. 

 

1.  Remove the burner and mounting plate. 

2.  Inspect the heat exchanger using a mirror inserted through the 

burner opening. 

3.  Using a brush on a flexible handle, loosen the soot on the inside 

of the heat exchanger. 

4.  Remove the soot with a vacuum.  

5.  See page 25 for locations. Remove the heat exchanger cleanout 

cover or flue collector box. Using a brush on a flexible handle, 
loosen the soot from the heat exchanger surfaces. Remove as 
much soot as possible using a vacuum. 

6.  Replace cleanout cover or flue collector box. 

7.  Re-install burner and mounting plate. 

Obtain gas-tight seals at burner flange and cleanout 
plates to prevent possible flue gas leakage and 
carbon monoxide emissions, leading to severe 
personal injury or death. 

 

Inspect vent system 

Thoroughly inspect the entire vent system at least annually, 
including horizontal vent pipe and chimney or vertical vent. Ensure 
vent system is repaired or replaced if necessary before placing 
furnace in operation. 
 

Oiled-bearing burner motors 

The burner may need to be lubricated if the motor is equipped with 
oiling cups. Refer to burner manual for specific instructions. If 
instructed, apply a few drops only of S.A.E. 20 detergent oil (never 
use household oils). Do not attempt to “fill up” the oil cup. Over-oiling 
can damage the motor. 
 

 
 

Optional Blocked vent shut off (BVSO) cleaning 

For continued safe operation, the Blocked Vent Shut Off System 
(BVSO) is required to be inspected and maintained annually by a 
qualified agency. 

1. 

Disconnect the power to the appliance; 

2. 

Remove the two screws holding on the BVSO assembly 

cover; 

3. 

Remove the cover; 

4. 

Remove the two screws holding the thermal switch to the 

assembly base; 

5. 

Without removing the electrical wires, remove the thermal 

switch and remove any build-up from the thermal switch 
surface; 

D

Do not dent or scratch the surface of the 
thermal switch. If the thermal switch is 
damaged, replacement is required. 

6.  Clear and remove any build-up or obstruction inside the 

heat transfer tube; 

7. 

Re-mount the thermal switch to the assembly base; 

8. 

Re-attach the assembly cover with the screws removed in 

step 2; 

9. 

Re-establish power to the appliance.

 

 

Summary of Contents for PMP210

Page 1: ...sportation company by the consignee Do not store or use gasoline or other flammable liquids or vapors near this furnace or any other appliance Ventilate house while operating furnace for the first tim...

Page 2: ...o use gasoline a mixture of gasoline and oil waste fuel refuse or any other substance in the burner of furnace Installation 18 Do not block flow of combustion or ventilation air to furnace Do not bloc...

Page 3: ...aintained 2 Always apply whichever clearance is LARGER combustible construction or service accessibility Flooring and foundation Flooring If a combustible floor is used follow these instructions Upflo...

Page 4: ...yer and fireplace When outside air is used Connect each opening directly by ducts to the outdoors or to crawl or attic space that freely connects with outdoors Size per below Through outside wall or v...

Page 5: ...o avoid Spray cans containing chloro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for...

Page 6: ...The total drop through the duct system and air conditioning condensing coil if used must not exceed 0 5 water column See suggested duct sizing in this manual For more detailed sizing information refer...

Page 7: ...he cause of this shut down Refer to the figures 5 6 at section 6 Wiring Diagrams and detailed instructions supplied with the BVSO for the installation and wiring procedures It is also essential that t...

Page 8: ...furnace installed with a 4 ton air conditioning evaporator coil Heating mode airflow is still 1 050 CFM Cooling mode airflow use Equation 3 4 CFM 4 x 400 1 600 CFM The larger number is 1 600 CFM cool...

Page 9: ...7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 13...

Page 10: ...600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 120...

Page 11: ...nal injury or death 1 The horizontal vent must slope upwards away from the furnace a minimum of inch per foot 2 Connection must be made above bottom of chimney to avoid blockage Vent pipe must not ent...

Page 12: ...use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal injury dea...

Page 13: ...PMP Oil Furnaces Furnace Manual 670 000 003 1010 13 Notes...

Page 14: ...t must be used Supply wiring to furnace must be sized for the load required see Section 12 p 27 Provide electrical ground at furnace as required by codes Connect 120 VAC 60 Hertz single phase separate...

Page 15: ...ure 5 Blocked Vent Shut Off device wiring Optional 1 Blocked Vent Shutt Off device BVSO 2 Electrical kit supplied 3 Connect one red wire to limit switch 4 Disconnect red wire from limit switch and con...

Page 16: ...PMP Oil Furnaces Furnace Manual 16 670 000 003 1010 6 Wire furnace burner continued Figure 6 Wiring PMP furnace with direct drive blowers Beckett Carlin and Riello burners...

Page 17: ...nd 11 with 0 smoke To start furnace continued Make final burner adjustments using combustion test equipment to assure proper operation 8 Check furnace and duct system for proper operation and conditio...

Page 18: ...lector box to prevent possible flue gas leakage and carbon monoxide emissions leading to severe personal injury or death 24 Was Limit Control tested per To start up in this manual 25 Was furnace cycle...

Page 19: ...ignment of the cad cell to assure it is aimed at the fire Check nozzle and electrode position Check ignition transformer output Reference burner manufacturers instructions Check tube insertion and ali...

Page 20: ...NING and guidelines given on page 21 Failure to comply could result in severe personal injury death or substantial property damage Consult with homeowner to see if there were any Check sequence of ope...

Page 21: ...e it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh...

Page 22: ...handle loosen the soot from the heat exchanger surfaces Remove as much soot as possible using a vacuum 6 Replace cleanout cover or flue collector box 7 Re install burner and mounting plate Obtain gas...

Page 23: ...west setting Burner should turn off 6 Furnace blower will continue to run until the Limit Fan switch senses air temperature below the fan OFF setting 7 Set the room thermostat to call for heat again A...

Page 24: ...PMP Oil Furnaces Furnace Manual 24 670 000 003 1010 Notes...

Page 25: ...PMP Oil Furnaces Furnace Manual 670 000 003 1010 25 Components and Replacement Parts...

Page 26: ...PMP Oil Furnaces Furnace Manual 26 670 000 003 1010 11 Components and replacement parts Figure 7 Model PMP 210 furnaces Component locations B50110 Rev A...

Page 27: ...R004 33 15 MF capacitor L01I005 10 Limit Control cover B02826 01 34A Electronic fan timer R99G004 11 Gasket smoke box B02714 34B Electrical wire harness board B02797 12 Smoke box cover B02799 01 35 Ro...

Page 28: ...e quantity load ampacity for fuse size weight o F and size amps wiring sizing amps pounds PMP 210 65 85 1 20 X 30 115 60 1 15 7 18 1 20 0 250 Model Volt Hertz Phase DNS 0909 Rev A Maximum cooling capa...

Page 29: ...1 50 1 50 60B 100 1 50 PMP 210 1 10 1 25 1 35 1 50 1 35 1 50 CARLIN BURNER EZ 1 Tube insertion 2 1 2 Model Input Firing rate USGPH Nozzle Delavan Head Setting A BECKETT BURNER Model AFG 3450 RPM Tube...

Page 30: ...om thermostat 2 If the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary...

Page 31: ...PMP Oil Furnaces Furnace Manual X40104 Rev I...

Reviews: