PMP
Oil Furnaces
–
Furnace Manual
18
670-000-003/1010
8
Checkout procedure
(continued)
Vent and combustion air
..10. Was existing chimney/vent system inspected and found in
proper condition?
..11. Was new vent piping installed and sealed as required?
.. 12. Was vent sizing checked against furnace manual and codes?
Ductwork
..13. Was duct sizing checked against furnace manual and/or
ACCA Manual D?
..14. Were supply and return registers checked for size based on
airflow?
..15. Were balancing dampers installed as needed?
..16. WAS ductwork sealed and insulated as needed?
Furnace operation
..17. Is a/ Are clean air filter(s) in place?
..18. Was temperature rise through furnace checked (not to
exceed 85
o
F) and blower speed adjusted if necessary?
..19. Was thermostat heat anticipator set per wiring diagram?
..20. Was burner started and tested per burner manual?
..21.
Is there proper draft and burner flame? Were final
adjustments made with combustion test equipment?
Furnace operation
(continued)
.. 22. Was air purged from oil piping and piping checked for leaks?
.. 23. Ws burner sealed to furnace and nuts tightened? Was
burner harness securely plugged in?
Obtain gas-tight seals at burner flange, cleanout
plates and/or flue collector box to prevent possible
flue gas leakage and carbon monoxide emissions,
leading to severe personal injury or death.
.. 24. Was Limit Control tested per “To start up” in this manual?
.. 25. Was furnace cycled with thermostat? Raise to highest
setting and verify the furnace goes through normal start up
cycle. Lower to lowest setting and verify furnace shuts off.
.. 26. Were several operating cycles observed for proper operation?
.. 27. Were room thermostat(s) set to desired room temperature?
After installation
.. 28. Was “Installation and service certificate” (below) filled out?
.. 29. Was Owner’s information in this manual reviewed with
owner or maintenance person and the person instructed to
keep the manual for future reference?
.. 30. Were all instruction manuals placed near the furnace for
future reference?
Installation and service certificate
Furnace model
__________________________________________________
Series
_______________________
Serial number
_______________________________________
Date installed
_____________________________
Installation instructions have been followed.
Checkout sequence has been performed.
Above information is certified to be correct.
Information received and left with owner/maintenance person.
Installer ______________________ ________________________ _____________________
(Company)
(Address)
(Phone)
________________________________________________
(Installer’s
signature)