background image

 

10 

 

4.  Check the gas pressure and settings. 

Minimum Burner Pressure Setting 

a.  Set LOW burner capacity by pressing button Z2 

b.  Connect a micro manometer to the test gauge B (Figure 8) 

c.  Rotate the internal screw “D” (Figure 8) and set the pressure at the correct value 

Maximum Burner Pressure Setting: 

a.  Set HI burner capacity by pressing button Z2 

b.  Connect a micro manometer to the test gauge B (Figure 8) 

c.  Rotate the external screw “C”  (Figure 8) and set the pressure at the correct value 

Gas Supply 

Check all local codes for requirements, especially for the size and type of gas supply line required. On natural gas lines less than 
15” (380 mm) long, use 1/2” tube; on longer runs, use 3/4” iron tube or equal. On LP Gas lines please consult LP Gas supplier. 

Installing a New Main Gas Shutoff Valve 

Each furnace should have its own manual gas shutoff valve. A manual main gas shutoff valve should be located in the vicinity of 
the  furnace.  Where  none  exists,  or  where  its  size  or  location  is  not  adequate,  contact  your  local  authorized  installer  for 
installation or relocation. 

Compounds used on threaded joints of gas piping must be resistant to the action of LP Gas. The gas lines must be checked for 
leaks  by  the  installer.  This  should  be  done  with  a  soap  solution  watching  for  bubbles  on  all  exposed  connections,  and  if 
unexposed, a pressure test should be made.  Correct all gas leaks before operating the furnace. 

Never use an exposed flame to check for leaks. The furnace must be disconnected from piping at inlet of control valve 
and  pipe  capped  or  plugged  for  a  pressure  test.  Never  pressure  test  with  furnace  connected;  the  control  valve  will 
sustain damage! 

A  gas  shutoff  valve  and  ground  joint  union  should  be  installed  in  the  gas  line  upstream  of  the  gas  control  valve  to  aid  in 
servicing.  It  is required by  the National Fuel Gas Code that a drip  line  be  installed near the  gas  inlet. This should consist of a 
vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles 
may collect. 

Use of the following gas connectors is recommended: 
– ANSI Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings. CGA 6.10. 
– ANSI Z21.45 Assembled Flexible Appliance Connectors of Other Than All–Metal Construction. 
The above connectors may be used if accepted by the authorities having jurisdiction. 

Pressure Testing of the Gas Supply System 

1.  To check the inlet pressure to the gas valve, a plugged tapping, accessible for a test gauge connection, is provided on the 

gas valve. (Figure 8 - A). 

2.  The furnace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure 

testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). 

3.  The furnace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any 

pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). 

Attention

: If one of the above procedures results in pressures in excess of 1/2 psig (14” w.c.; 3.5 kPa) on the furnace gas valve, 

it will result in a hazardous condition. 

High Altitudes (US Only) 

For altitudes/elevations above 2,000 feet (610 m), ratings should be reduced at the rate of 4-percent for each 1,000 feet (305 m) 
above  sea  level  by  reducing  the  manifold  pressure  at  8%  rate  on  the  gas  supply.  Maximum  altitude  allowed  for  installation  is 
5,500 feet (1680 m). 

High Altitudes (Canada Only) 

The furnace is tested according to CGA 2.17 M91 for installation between 0 and 4,500 ft (0 and 1370 m) altitude. For 
altitudes/elevations above 2,000 feet (610 m), ratings should be reduced at the rate of 4-percent for each 1,000 feet (305 m) 
above sea level by reducing the manifold pressure at 8% rate on the gas supply. Maximum altitude allowed for installation is 
5,500 feet (1680 m).  
 
 

Summary of Contents for 1773511

Page 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 1773512 MODEL Propane Gas Only 1773511...

Page 2: ...d repair should be done by a QUALIFIED SERVICE TECHNICIAN The installation must conform to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI...

Page 3: ...qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas i...

Page 4: ...is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recommended when you do smell...

Page 5: ...in Canada with CAN CSA C22 2 No 3 Installations in the State of Massachusetts All installations in the State of Massachusetts must use the following requirements when installing maintaining or operat...

Page 6: ...e of the terminal 18 inches 46 cm minimum E Clearance to unventilated soffit 12 inches 30 cm minimum clearance to vinyl soffit 36 inches 90 cm minimum F Clearance to outside corner 12 inches 30 cm min...

Page 7: ...be length wall thickness 1 5 16 inches 7 9 mm 4 Drill the mounting holes A 5 holes in the wall If possible use self tapping screws drill 1 8 inch diameter holes If self tapping screws cannot be used d...

Page 8: ...end Mark the location of the three holes for the screw anchors Figure 7 The flue grid must be vertical 12 Remove the vent cap and drill all the necessary holes diameter inch for the screw fittings pro...

Page 9: ...r inserting the screwdriver as indicated by the arrow 3 Remove the nozzle from the support and replace it with the correct one Reassemble the nozzle assembly and the screw indicated at point 1 Set the...

Page 10: ...l Gas Code that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and fore...

Page 11: ...the furnace Checking the Gas Manifold Pressure The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve Figure 8 B The furnace comes set from t...

Page 12: ...otor Moteur du Ventilateur de Combustion SF Flame View Lamp green lamp Lampe de Presence de Flamme Verte SB Lock Out Lamp red lamp Lampe de Verrouillage Rouge TR Current Transformer 120 24 V Transform...

Page 13: ...ond attempt is STOP Read the safety information above on this label Set the thermostat to the lowest setting by turning it counterclockwise This appliance is equipped with an ignition device that auto...

Page 14: ...needs to be refilled after 4 5 days NOTE The use of water low in limestone or distilled is advisable in order to prevent any possible calcareous sedimentation that may be difficult to remove Anticalca...

Page 15: ...nnect the test gauge and firmly tighten the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted as instructed above Never adjust them independently...

Page 16: ...s 4 Check air flow switch 5 Clean and check exhaust flue pipe and air intake pipe 6 Check for gas leaks on all connections 7 Check and adjust gas pressure Check red O Ring Gasket NRNG003 If it is dama...

Page 17: ...tion Programmable day blocks 1 2 3 4 5 Monday Friday 1 2 3 4 5 6 Monday Saturday 1 2 3 4 5 6 7 Monday Sunday 6 7 Saturday Sunday KEY A On Off Switch Pos I The appliance is controlled by the room therm...

Page 18: ...proceeds one day at a time Number 1 stands for Monday number 2 stands for Tuesday etc C To set the time press the Hour Selector button h Figure 10 E to set the hour and the Minutes Selector button m F...

Page 19: ...button and select the program to be cancelled B Simultaneously press the Program Selector Figure 10 C and SKIP button Figure 10 G for at least 2 seconds The selected program will be cancelled C Verifi...

Page 20: ...ximum velocity Troubleshooting Step 2 Point 3 Z1 Z1 is down closed but there is no voltage on the fan motor M Check wiring and connections If everything is okay replace the switch Point 4 Z2 Z2 is dow...

Page 21: ...temperature is cold replace the switch Point 9 M1 M1 is open and fan thermostat temperature is lower than 140 F Check wiring connections gas pressure and fan motor Clean fan blades and air grids If e...

Page 22: ...control box Point 16 RP8 No flame sensing Check flame sensor wiring and connections SCheck gas pressure and exhaust flue pipe If everything is okay replace the flame control box Point 17 EV2 No voltag...

Page 23: ...inter Switch Part Number P332630 Z8 Z3 Timer and Manual Program Mode Switch Part Number P332629 Z2 Hi Lo Flame and Fan Speed Switch Part Number P332631 SF SB Green and Red Lamps Part Number P332538 P3...

Page 24: ...n Blower Motor Part Number P332514 M1 Overheat Thermostat Part Number P332565 M2 Fan Thermostat Part Number P332496 Fan Blades 4 pieces Part Number P332572 Left P332638 Right M Fan Motor 2 Pieces Part...

Reviews: