background image

 

Safety Rules

 

 
 

 

 

WARNING:

  READ  THESE  RULES  AND  THE 

INSTRUCTIONS  CAREFULLY.  FAILURE  TO 
FOLLOW  THESE  RULES  AND  INSTRUCTIONS 
COULD  CAUSE  A  MALFUNCTION  OF  THE 
FURNACE.  THIS  COULD  RESULT  IN  DEATH, 
SERIOUS  BODILY  INJURY  AND/OR  PROPERTY 
DAMAGE. 

Installation  must  conform  to  local  codes.  In  the  absence  of  local 
codes, installation must conform with the National Fuel Gas Code, 
ANSI  Z223.1.  The  appliance,  when  installed,  must  be  electrically 
connected and grounded in accordance with local codes or, in the 
absence  of  local  codes,  with  the  current  National  Electrical Code 
ANSI/NFPA NO. 70. 

In Canada

:  

1.  Installation  must  conform  to  local  codes  or,  in 

the  absence  of  local  codes,  the  current 
CAN/CGA B149 installation code. 

2.  The  appliance,  when  installed,  must  be 

electrically 

connected 

and 

grounded 

in 

accordance with local codes or, in the absence 
of  local  codes,  with  the  current  CSA  C22.1 
Canadian Electrical code.  

3.  Reference is made in this manual regarding gas 

type  as  L.P.G.  Be  advised  that  L.P.G.  is  not 
available in Canada, refer to propane/L.P. Gas. 

 

1.  Use  only  manufacturer's  replacement  parts.  Use  of  any 

other parts could cause injury or death. 

2.  DO NOT install this furnace where it could be isolated by 

closing doors to the heated space. 

3.  DO NOT install this furnace in a travel trailer or 

recreational vehicle. 

4.  MAINTAIN  all  clearances  specified  in  section  "Locating 

Wall Furnace and Thermostat". 

5.  BE  SURE  this  furnace  is  for  type  of  gas  to  be  used. 

Check  the  rating  plate  by  the  gas  valve  in  the  lower 
cabinet. Do not change it to use other gases. 

6.  For  natural  gas,  the  minimum  inlet  gas  supply  pressure 

for  the  purpose  of  input  adjustment  is  5"  water  column. 
The  maximum  inlet  gas  supply  pressure  is  7"  water 
column. 

For L.P. Gas, the minimum inlet gas supply pressure for 
the purpose of input adjustment is 11" water column. The 
maximum inlet gas supply pressure is 13" water column. 

7.  Any  safety  screen,  guard  or  parts  removed  for  servicing 

this  appliance  must  be  replaced  prior  to  operating  the 
appliance  to  avoid  property  damage,  bodily  injury  or 
death. 

8.  Install  the  furnace  vent  directly  to  the  outdoors  so  that 

harmful combustible flue gases will not collect inside the 
building.  Follow  the  venting  instructions  for  your  type  of 
installation  exactly.  Use  only  the  type  and  size  of  vent 
pipe and fittings specified.  

9.  BE  SURE  to  provide  for  adequate  combustion  and 

ventilation air. The flow of this air to the furnace must not 
be blocked. 

10.  NEVER vent flue gases into another room, a fireplace or 

any  space  inside  a  building.  This  could  cause  property 
damage, bodily injury or death. 

11.  Never test for gas teaks with an open flame. Use a soap 

solution to check all gas connections. This will avoid the 
possibility of fire or explosion. 

12.  ALLOW the furnace to cool before servicing. Always shut 

off electricity and gas to furnace when working on it. This 
will prevent any electrical shocks or burns. 

13.  DUE TO HIGH TEMPERATURES, locate the furnace out 

of traffic and away from furniture and draperies. 

14.  ALERT children and adults to the hazards of high surface 

temperatures  and  warn  them  to  keep  away  to  avoid 
burns or clothing ignition. 

15.  CAREFULLY  supervise  young  children  when  they  are  in 

the same room with the furnace. 

16.  DO NOT place clothing or other flammable material on or 

near furnace. 

17.  INSTALLATION and REPAIR must be done by a qualified 

service  person.  The  appliance  should  be  inspected 
before  use  and  at  least  annually  by  a  professional 
service person. More frequent cleaning may be required 
due  to  excessive  lint  from  carpeting,  bedding  material, 
etc.  It  is  imperative  that  control  compartments,  burners 
and  circulating  air  passages  be  kept  clean.  Failure  to 
keep  burner-control  compartment  and  other  parts  of 
furnace  clean  can  cause  dangerous  conditions  to 
develop which can cause injury and even death. 

18.  BEFORE INSTALLING: To avoid electrical shock, tum off 

electrical  circuits  that  pass  through  the  wall  where  you 
are going to install the furnace. 

19.  BE AWARE of good safety practices by wearing personal 

protective equipment such as gloves  and  safety  glasses 
to avoid being injured by sharp metal edges in or around 
furnace and while cutting or drilling holes in wood and/or 
sheet metal. 

20.  CAUTION:  Label  all  wires  prior  to  disconnection  when 

servicing controls. Wiring errors can cause improper and 
dangerous  operation.  Verify  proper  operation  after 
servicing. 

Always shut-off electricity to furnace when working on it. 
This will prevent any electrical shocks or burns. 

21.  DO NOT store or use gasoline or other flammable liquids 

or vapors near the furnace. 

WARNING: 

Do not use this furnace if any part has 

been  under  water.  Immediately  call  a  certified 
service  technician  to  inspect  the  furnace  and  to 
replace any part of the control system and any gas 
control which has been under water. 

Summary of Contents for 1753012

Page 1: ...l switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot r...

Page 2: ...improper installation 4 This warranty does not cover claims which do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified inst...

Page 3: ...llation 6 17 Locating Your Wall Furnace 6 Thermostat Installation 9 Cabinet Installation 11 Vent Installation 11 Gas Supply and Piping J 14 Operating Your Furnace 18 20 Operating Instructions 18 Start...

Page 4: ...pecified 9 BE SURE to provide for adequate combustion and ventilation air The flow of this air to the furnace must not be blocked 10 NEVER vent flue gases into another room a fireplace or any space in...

Page 5: ...d Hand drill or properly grounded electric drill 6 ft folding rule or tape measure Screwdrivers Phillips Head Pliers wire cutting Stud locator or small finishing nails Tin snips 8 and 12 inch adjustab...

Page 6: ...lectrical outlet can be brought to the furnace 6 Select a location that will provide adequate accessibility clearance for servicing and proper operation Interior Clearances Figure 2 1 The unit is desi...

Page 7: ...g center mark all the way through to the outside Cut the 2 1 2 inch diameter hole through the inside wall Using the 1 4 inch hole as center cut a matching hole in the outside wall It may be better to...

Page 8: ...fter cutting the vent and gas openings place the rear panel back onto the wall and screw into place using the supplied mounting screws The screws should go into the wall studs as there are enough clea...

Page 9: ...drilling a hole in the wall at the selected location drive a small finishing nail through the ceiling in the comer of the wall and ceiling above the thermostat location Pull the nail out and push a s...

Page 10: ...3 Push any excess wire back through hole in the wall and plug the hole with insulation to prevent drafts from affecting thermostat operation 4 Being sure to level thermostat for the best appearance F...

Page 11: ...VC meeting ASTM Standard D1784 For Canada ULC S636 approved duct must be used Use a 45 elbow as the vent termination for the exhaust pipe vent terminations are not counted towards the overall vent len...

Page 12: ...Installation 12 FIGURE 16 FIGURE 17 FIGURE 18 FIGURE 19...

Page 13: ...to attach the PVC pipe to the inducer fan and tighten the hose clamps shown in Fig 21 If PVC pipes will be exposed to freezing temperatures the pipes must be insulated using Armaflex or similar insul...

Page 14: ...burners must not exceed the rated input and pressure shown on the rating plate For natural gas the manifold pressure should be 3 2 inches water column The manifold pressure should be 10 inches water...

Page 15: ...On L P gas installations use a compound resistant to action of liquefied petroleum gases 3 Use ground joint unions 4 Install a drip leg sediment trap to trap dirt and moisture before it can enter the...

Page 16: ...cified pressures for testing Higher pressures may damage the gas valve and cause over firing which may result in combustion chamber failure Liquefied petroleum gas L P G is heavier than air and it wil...

Page 17: ...you have a question regarding the amount of fuel consumed call your local gas utility or gas supplier WARNING DO NOT TAMPER WITH THE REGULATOR OR BURNER ORIFICES AS PROBLEMS RESULTING FROM THERE MAY C...

Page 18: ...safety information above 2 Make sure there is power to the unit the furnace is supplied with a 3 prong 120VAC power cord The internal switches must be on see fig 31 and 32 3 The furnace has 3 modes of...

Page 19: ...level The display panel will show the word SET on the top right corner After this sequence the display panel will show heat level 6 Local Mode After setting a desired room temperature on the display...

Page 20: ...re To measure the input using the gas meter proceed as follows 1 Turn off the gas supply to all other appliances except the furnace 2 With the furnace operating time the smallest dial on the meter for...

Page 21: ...t panel Using a low profile tray to collect water place underneath the trap and unscrew the bottom of the trap After condensate is collected replace the bottom of the trap replace front panel and rest...

Page 22: ...er Description Qty 1 6H24 Inner Frame 1 2 6H03 Bottom Support Cover 1 3 6H01 Heat Exchanger Support 1 4 P323702 17 5K Heat Exchanger Asy 1 5 6H13 Blower Housing Support Right 1 6 6H12 Blower Housing D...

Page 23: ...Replacement Parts List 34 6H31 Front Panel 1 35 P323465 Nylon PCB Standoff 4 36 P323481 Inducer Fan Mounting Screw 4 37 P323459 Fan Motor 1 38 P323460 Blower Wheel 1...

Page 24: ...24 Page left blank intentionally...

Page 25: ...Page left blank intentionally...

Page 26: ...Wiring Diagram 26...

Page 27: ...eing fastened to an uneven wall Vent tube and air inlet tube may be in a bind with a vent cap assembly Be sure the hole through the wall is correct and parts fit without binding 5 Noisy Blower A Housi...

Page 28: ...liance Do not touch any electrical switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone If you cannot reach y...

Reviews: