Net
User Manual 7.1 (2019-04) 18
Subject to change
CAN-out
CAN-in
Motor module
BS2-MO-01
CAN
CAN
BS2-MO motor modules
⇒
see page 2 (MVV-TB, MBO)
The motor module makes it possible to connect on or two fire dampers and/or smoke protection dampers with electrical
24 V spring return actuator, integrated limit switches and thermo-electric release for fire dampers.
The module monitors the operating status of the dampers, with functional tests checking that they are fully functional.
The dampers are closed and opened again. In the process, the run times and current consumption values of the
motors are measured, and changes can thus be detected in good time. Local functional tests can thus be replaced
1)
. Calendar controls facilitate automatic functional tests. The results of the functional check are stored reliably and
permanently on the module, and in the Wildeboer-Net software after downloading.
A functional check can be started locally using a motor module, regardless of the status of commissioning of the
overall system, in order, for example, to check directly after installation that the fire damper is connected properly and
to make sure that the fire damper is fully functional.
⇒
see page 10
The motor modules can be parametrised to perform uninterruptible release controls (
⇒
see page 12
) if, for example,
other fire dampers have to close when a particular one is closed and if fans have to be switched off.
All actuations and functions are remote-controlled or controlled using the motor module’s push buttons. Fire dampers
can be opened so long as they have not been permanently closed by thermo-electric tripping.
•
Operating voltage for 24 V DC spring return actuators from the module.
Current consumption
≤
0.5
A, start-up currents
≤
5.8
A and
≤
5
ms. Electronic protection against
overcurrent, and undervoltage detection.
Types by connections:
•
BS2-MO-01 for AMP connector of fire dampers.
•
BS2-MO-02 for duct connections with plug-in screw terminals.
•
BS2-MO-03 for AMP connector of a fire damper and with plug-in screw terminals
for the second fire damper or smoke protection damper.
All the benefits of Wildeboer-Net can also be applied for the FK90 fire damper for
commercial kitchens, in the same way as the motor modules. For this purpose, the
FK90 fire damper for commercial kitchens can be order for connection to the Wildebo-
er-Net with FKKUE-03 control unit (
⇒
see user manual 5.0-1
). The fire damper is supplied
pre-installed with the control unit fitted.
7
8 7 8
BS2-MO-01 Connection of fire dampers directly to a motor module
Motor connecting lines approx. 0.75 m
Wildeboer-Net
Products (3)
1)
The local inspection by a specialist inspector for special construction, as required every 3 years in accordance with the model inspection code
(MPrüfVO), is excepted from this provision.
FK90 fire damper for commercial kitch-
ens with FKKUE-03 control unit