Net
BSK 1
Manual ON/OFF
BSK 1
Manual ON/OFF
BSK 1
open/close
BSK 1
open/close
BSK 1
opened
BSK 1
opened
BSK 1
closed
BSK 1
closed
BSK 1
opened
BSK 1
closed
BACnet
Wildeboer-Net
1 data point
1 data point
1 data point
1 data point
1 data point
1 data point
Gateway
Modbus
User Manual 7.1 (2019-04) 23
Subject to change
Protocol
Gateway
WiNet-GW-01 WiNet-GW-02 WiNet-GW-03 WiNet-GW-04 WiNet-GW-05 WiNet-GW-06
BACnet MS/TP
1)
x
x
x
x
x
x
BACnet IP
x
x
x
x
x
x
Modbus/serial (ASCII & RTU)
1)
x
x
x
x
x
x
Modbus/IP
x
x
x
x
x
x
OPC Server DA 2.0
x
x
x
x
x
x
LON
x
x
KNX/TP
x
x
Data points
200
1100
200
1100
200
1100
Gateways are used for communication between devices which have different communication protocols. A WiNet-GW
gateway enables the connection of Wildeboer-Net to the following open communication protocols. Different protocols
can also be operated simultaneously with a single gateway.
Data point definition
⇒
see page 8
Information is exchanged between devices with different communication protocols via data points. A data point, for
example, is the position indicator
“fire damper (BSK) opened”
. If a data point of the Wildeboer-Net system is not only
ported to one other protocol via the gateway, but to several protocols, more data points are required accordingly.
Wildeboer-Net provides a large number of data points. The Wildeboer-Net software is used to configure which data
points are to be transferred from Wildeboer-Net to the target system.
The number of data points initially available is predetermined by the type of device and the licence.
The number of data points can be upgraded to 2500 with a license update.
1)
not possible simultaneously
Wildeboer-Net