8. Configuration via display and operating unit
8.1.2
Configuring level measurement
Requirement
■
Length unit for the filling height is known
■
The density of the medium is known
1.
Open the operating menu with [↵].
Select “Basic setting” and confirm with [↵].
2.
Select “Application” and confirm with [↵].
3.
Select “Level” and confirm with [↵].
4.
Select “Unit” and confirm with [↵].
5.
Select length unit and confirm with [↵].
»
Length unit is set.
6.
Select “Density” and confirm with [↵].
7.
Select “Density unit” and confirm with [↵].
8.
Select density unit and confirm with [↵].
»
Density unit is set.
9.
Select “Density value” and confirm with [↵].
10.
Set digit using [▲] [▼] and confirm with [↵].
»
The cursor moves to the next digit.
»
Repeat for each digit.
»
Density value is set.
11.
Go back two menu levels using [ESC].
Select “Mode” and confirm with [↵].
12.
Select “Level” and confirm with [↵].
»
Mode is set.
13. Perform a mounting correction.
→ See chapter 8.5 “Mounting correction (offset)”.
» Level measurement is configured.