15
4 Mounting
WIKA Operating Instructions - Differential pressure transmitter DPT-20
Higher process temperatures often mean also higher ambient
temperatures. Make sure that the upper temperature limits stated in
chapter "
Technical data
" for the environment of the electronics hous-
ing and connection cable are not exceeded.
4.2 Instructions for oxygen applications
Oxygen and other gases can be explosive when brought into contact
with oils, grease and plastics, so the following measures must also be
taken:
•
All components of the system, e.g. measuring instruments, must
be cleaned in accordance with the requirements of recognized
regulations or standards
•
Depending on the seal material, certain temperatures and pres
-
sures must not be exceeded in oxygen applications, see chapter "
Technical data
"
Danger:
Instruments for oxygen applications must be unpacked just before
mounting. After removing the protective cover of the process fitting,
the label "O
2
" will be visible on the process fitting. Penetration of oil,
grease and dirt should be avoided. Danger of explosion!
4.3 Connection to the process
DP flow elements are installations in pipelines which generate a
flow-dependent pressure drop. The flow rate is measured via this dif
-
ferential pressure. Typical DP flow elements are Venturi tubes, orifice
plates or impact pressure probes.
Instructions for mounting the DP flow elements are stated in the ap
-
propriate standards as well as in the documentation from the respec-
tive manufacturer.
Effective pressure lines are pipelines with a small diameter. They are
used to connect the differential pressure transmitter to the pressure
tapping point or the DP flow element.
Principles
Effective pressure lines for gases must always remain completely dry
and no condensate must collect. Effective pressure lines for liquids
must always be completely filled and must not contain any gas bub
-
bles. Therefore, suitable venting systems must be provided for liquids
and suitable drainage systems for gases.
Wiring
Effective pressure lines must always run with a sufficient, strictly mo
-
notonous slope/gradient of at least 2 %, but better up to 10 %.
Recommendations for wiring of effective pressure lines are stated in
the corresponding national and international standards.
Connection
Effective pressure lines are connected to the device via standard cut
-
ting ring screw connections with suitable thread.
Temperature limits
Oxygen applications
DP flow element
Effective pressure lines