Installation, operating and maintenance manual
UNIGAS 300
DDG6004MHGB/08-2017/Rev.A2 Software version from M 1.3.40 and D 2.3.37
49
Status messages
Exceeding of alarm Q
b1
Flow rate converted volume, configurable between 1 and 10,000
m
3
/h
Exceeding of warning Q
b1
Flow rate converted volume, configurable between 1 and 10,000
m
3
/h
Exceeding of alarm V
b1
_60
Converted consumption in clock hour, configurable between 1 and
10,000 m
3
Exceeding of warning V
b1
_60
Converted consumption in clock hour, configurable between 1 and
10,000 m
3
Exceeding of alarm Q
c1
Flow rate corrected unconverted volume, configurable between 1
and 10,000 m
3
/h
Exceeding of warning Q
c1
Flow rate-corrected unconverted volume, configurable between 1
and 10,000 m
3
/h
Exceeding of alarm V
c1
_60
Corrected unconverted consumption in clock hour, configurable
between 1 and 10,000 m
3
Exceeding of warning V
c1
_60
Corrected unconverted consumption in clock hour, configurable
between 1 and 10,000 m
3
Exceeding e of volume difference
between counters 1 and 2
Configurable between 1 and 100 m
3
Exceeding of alarm p
max
Configurable between 800 and 100,000 mbar
Exceeding of alarm p
min
Configurable between 800 and 100,000 mbar
Exceeding of alarm t
max
Configurable between -50 and 100 °C
Exceeding of alarm t
min
Configurable between -50 and 100 °C
Alarm input 1
Open contact recorded on alarm input 1
Alarm input 2
Open contact recorded on alarm input 2
Status messages regarding:
- metrology
- inputs and outputs
- clock
- opening of housing
- calibration lock
- log books
- volume difference
- electrical power supply
Clock
Type
POSIX
Summer / winter time (DST)
In accordance with 2000/84/EC
Typical accuracy
20 ppm at 25 °C