Recovery cylinder cooling method
7.1.
P
RE
-
WORK
C
OOLING METHOD
a) Before starting, there must be at least 0,5 kg of liquid refrigerant in the cylinder
b) Make sure all connections are correct and tight (refer to the below picture)
c) Make sure the
OUTPUT
valve and
INPUT
valve are on position CLOSE.
d) Turn the
Recover/Purge
valve to position "Recover".
e) Power on and then press the
START
key to start the unit.
f) Open the Vapour and Liquid valves on the recovery cylinder.
g) Open the
OUTPUT
valve, then open the
INPUT
valve.
h) Regulate the
OUTPUT
valve so that the output pressure is 7 bar higher than the input pressure,
but never more than 21 bar
i)
Run until the cylinder is cold; then turn the unit off.