IMPORTANT - WARNING
In case you perform recovery/recycling cycles of high quantities of liquid refrigerant (more than 2kg),
regulate the input flow by turning the INPUT valve so that the pressure read on the M1 pressure gauge
does not exceed 6 bar
b)
Turn the
V1
valve to position
Recovery/Recycling
c)
Turn the
INPUT
valve to position ”CLOSE”. Make sure that the valve
Recover/Purge
is
on the RECOVER position.
d)
Connect the valve of the T2 hose (delivery) to the stocking cylinder
e)
Open the valves on the manifold (not supplied with the recovery unit)
f)
Open the valve on the stocking cylinder
g)
Open the
T1
and
T2
flexible hoses valves (flexible hoses are not supplied with the unit)
h)
Turn the
Power Switch
to position “ON”
i)
Turn the
BY-PASS
switch
to position MANUAL
j)
Turn the
OUPUT
valve to position “OPEN”
k)
Slowly turn the
INPUT
valve to position “OPEN”.
l)
Press the
START
key to start the unit
m)
In case you perform recovery/recycling cycles of high quantities of liquid refrigerant
(more than 2kg), regulate the input flow by turning the INPUT valve so that the pressure
read on the M1 pressure gauge does not exceed 6 bar
n)
If the unit fails to start, turn the
INPUT
valve to position "CLOSE", restart the unit by
pressing the
START
key and slowly open the
INPUT
valve.
o)
Let the unit run until you reach a pressure of 2 bar on the
M1
gauge. Stop the unit by
means of the
Power switch
p)
Connect the oil drain hose to the
V3
valve situated on the rear of the unit.
q)
Slowly open the valve until all the oil inside the unit is drained. At the end of this
operation, turn the V3 valve to close it.
r)
Re-start the Recovery/Recycling function by pressing the
START
key.
s)
Run until desired vacuum is achieved or until the unit stops automatically (the “
BY-PASS
switch” is on the “AUTO” position”).
t)
Close the vapour and liquid ports of the manifold.
u)
Turn the
INPUT
and
OUTPUT
valves to position “CLOSE”
v)
Turn the recovery unit off.
WARNING
Always purge the unit after each use. Failure to purge the remained refrigerant from the unit could result
in the acidic degradation of internal components and ultimately cause premature failure of the unit.