Meter Connection: Confirm the cable connected to the meter is strictly by the label as
below.
Checking After Turn On AC Power And Battery Power
★
Battery Connection: BAT led on inverter should be green.
★
On-Grid & Back-Up Connection: Grid led and EPS led on inverter should be green.
★
Meter Connection
:
After turn on AC power, the GRID led on inverter should be
green.
★
Communication:
1.
if connection between inverter and wifi stick is OK.
Note: 5 minutes After turn on AC power, the COM led on inverter should be green. You
can see your SPA in eCactus APP/Web.
Note:
Note: If any led on inverter is red, then please refer to the
SPA QUICK INSTALLATION INSTRUCTIONS.
Possible Problems During Operation SPA not Start Up With ONLY Battery
Solution:
1.
Make sure the voltage of battery is higher than 85V, otherwise battery cannot start
SPA up.
No Discharge or Output From SPA to Support Loads.
Possible Reasons:
1.There is grid-tied inverter connected in the system, and the output power is higher
than load power.
2.Battery is not on the condition of discharging, such as low SOC, battery
communication fail for lithium batteries etc.
Solutions:
1.Communication between SPA and Meter is OK or not