4
Technical Data
Supply circuit (A1, A2)
min.
typ.
max.
Operating voltage U
B
AC/DC 24 V
20.4 V
—
26.4 V
Residual ripple DC Uss
—
—
2.4 V
Rated power
—
1.6 W / 2.9 VA
—
Peak current I
Peak
—
—
1.5 A
Operating voltage U
B
AC 42 - 48 V
AC 35.7 V
—
AC 52.8 V
Rated power
—
2.3 W / 2.6 VA
—
Operating voltage U
B
AC 115 - 120 V
AC 97.8 V
—
AC 126.5 V
Rated power
2.2 W / 2.5 VA
Operating voltage U
B
AC 230 V
AC 195.5 V
—
AC 253 V
Rated power
2.1 W / 2.4 VA
Fuse
T 0.5 A (time lag)
Rated frequency AC
50 Hz
—
60 Hz
Output circuit (S11, S21)
Output voltage
—
—
DC 40 V
Short-circuit behavior
absolutely short-circuit proof
Input circuits S12 and S52/S22
Input voltage U
e
19.2 V
—
26.4 V
Input current I
e
—
25 mA
—
Input peak current I
e,peak
—
—
100 mA
Conductor resistance
—
—
25
Ω
Release time t
R
—
—
10 ms
Recovery time t
W
—
—
750 ms
Interrupt time of U
e
(test pulses), t
TP
—
—
1 ms
Period of interrupt time
25 ms
—
—
Synchronous time t
S
—
—
∞
Input circuit S34
Input voltage U
e
19.2 V
—
26.4
Input current I
e
—
5 mA
—
Input peak current I
e peak
—
—
50 mA
Conductor resistance
—
—
25
Ω
Response time t
A1
—
150 ms
350 ms
Response time t
A2
—
50 ms
100 ms
Ready time t
B
350 ms
—
—
Interrupt time of U
e
(test pulses), t
TP
—
—
1 ms
Period of interrupt time
25 ms
—
—
Output circuit
Continous current I
n
—
—
8 A
(
*
)
Switching voltage U
n
—
—
AC 230 V
Switching load
—
—
2000 VA
Contact equipment
SNA 4043KE 3 Enabling paths (NO, positively driven)
1 Signalling path (NC, positively driven)
Contact material
AgSnO
2
Utilization category acc. EN 60947-5-1
AC-15: Ue AC 230 V, Ie 5 A
DC-13: Ue DC 24 V, Ie 5 A
Fuse
max 8 A / < 100 A²s
| in furnaces: max 6 A / < 100 A²s
Mechanical endurance
10
×
10
6
switching operations
General data
Creepage and clearance between circuits
acc. EN 60664-1
Rated surge voltage
4 kV
Overvoltage category
III
Contamination level
3 external, 2 internal
Rated voltage
AC 300 V
Test voltage U
eff
50 Hz
2 kV
Protection degree EN 60529 (housing / terminals)
IP 40 / IP 20
Ambient temperature working range / storage range
-25
°
C to +65
°
C / -25
°
C to +70
°
C
Weight DC devices / AC devices
0.21 / 0.25 kg
Terminals and connection
screw-type terminals
spring-type terminals
Single-core or finely stranded
1 x 0,2 mm² - 2,5 mm²
2 x 0,2 mm² - 1,0 mm²
2 x 0,2 mm² - 1,5 mm²
Finely stranded with wire-end ferrule to DIN 46228
1 x 0,25 mm² - 2,5 mm²
2 x 0,25 mm² - 1,0 mm²
2 x 0,25 - 1,5 mm² (trapezoid crimping)
Max. tightening torque
0,5 - 0,6 Nm (5-7 lbf-in)
--
Stripping length
7 mm
(
*
)
see diagram 1