4
Rapid assembly using basket trays
20
Wieland Electric GmbH | BA000369 (Rev. B) | 02/2016
4.1
Example using flat cable outlet
Attachment of component with assembly panel.
Bending of the clamping loops on the assembly panel.
Bending of the flat cable and closing of the flat cable outlet.
Termination of the outlet with the flat cable by screwing in the contact
screws.
Connection of the plug or functional module, lock and – done!
CAUTION
•
The contact screws must be screwed in until they meet the stop! The maximum tightening torque may not exceed 1 Nm.
•
The use of an electric or pneumatic torque driver is recommended. Phillips-head screwdriver, size 1, shaft length at least
45 mm. Matching screwdriver blade in accordance with DIN 3128, PH 1, Item No. 06.502.5200.0 The minimum connection tem-
perature for the EVA 7G4 mm² flat cable is -5°C. for the XLPE 7G4 flat cable, the minimum assembly temperature is + 5 °C.