Term

Location

Definition

Value

Pre-purge Time

N/A

Time intended to allow for the dissipation of any unburned 
gas or residual products of combustion at the beginning of 
a furnace operating cycle prior to initiating ignition.

15 sec

Adaptive Ignitor Warm 
up time

N/A

Adaptive algorithm that adjusts the duration of ignitor 
warm-up for the purpose of extending ignitor life. Following 
application of power, the warm-up time will be 17 seconds 
for the first 64 successful ignitions. Each subsequent warm-
up time will be decreased by 1 second until flame fails to 
be achieved (resulting in a retry) or until the minimum 5 
second warm-up period is achieved

17-19 sec

Trial for Ignition 
Period (TFI)

N/A

The period of time between initiation of gas flow and the 
action to shut off the gas flow in the event of failure to 
establish proof of the supervised ignition source or the 
supervised main burner flame.

4 sec

Ignition Activation 
Period (IAP)

N/A

Time between energizing the main gas valve and 
deactivation of the ignition means prior to the end of TFI.

3 sec

Flame Failure 
Response Time (FFRT)

N/A

Time between loss of the supervised main burner flame 
and the action to shut off the gas supply.

2 sec

Recycles

N/A

The additional attempts within the same thermostat cycle 
for ignition after loss of the supervised ignition source or 
the supervised main burner flame.

5 attempts

Retries

N/A

The additional attempts within the same thermostat cycle 
for ignition when the supervised main burner flame is not 
proven within the first trial for ignition period. The retry 
sequence will follow the inter-purge time.

4 attempts

Inter-purge

N/A

Time intended to allow for the dissipation of any unburned 
gas or residual products of combustion between the failed 
trial for ignition and the retry period.

60 sec

Post-purge Time

N/A

Time intended to allow for the dissipation of any unburned 
gas or residual products of combustion at the end of a 
furnace burner operating cycle. Post-purge begins at the 
loss of flame sense.

5 sec

Auto Restart

N/A

After one (1) hour of internal or external lockout, the control 
will automatically reset itself and go into an auto restart 
purge for 60 seconds.

60 min

Heat On Delay

N/A

Time between proof of the supervised main burner flame 
and the activation of the blower motor at Heat speed.

45/30* sec

Heat Off Delay

N/A

Time between the loss of a call for heat and the 
deactivation of the blower motor at Heat speed.

60/90/120*/
180 sec

Cool On Delay

N/A

Time between a thermostat demand for cool and 
energizing the circulator blower motor at Cool speed.

2 sec

Cool Off Delay

N/A

Time between the loss of a call for cool and the 
deactivation of the blower motor at Cool speed.

60*/2 sec

* = Default

    

DEFINITION OF TERMS 
& TIMING SPECIFICATION 

Summary of Contents for 50M56U-801

Page 1: ...climate com PART NO 37 7616B 37 7616A 1620 50M56 801 Integrated Furnace Control 2 Harness Assemblies Control Label Wire Ties Installation Instructions Electrical Specification 77 deg F 25 deg C Input...

Page 2: ...nnector Plug in remaining connections 74W03 103098 01 1195 100 1195 83 100A Follow Appliance Manufacturer s recommended installation or service instructions to ensure proper operation after installati...

Page 3: ...High Limit N C Aux N C Pressure Switch N O EAC 120V HUM 24V Twinning HUM 120V 120V Ignitor 120 VAC 24 VAC CLASS II TRANSFORMER 24 VAC TH TR Cool off Delay 60s 2s Heat on Delay 45s 30s 60s 120s 90s 18...

Page 4: ...g until Thermostat Satisfied Post Purge 25 seconds Blower Off Delay 60 90 120 180 Seconds System off Thermostat Inducer Pressure Switch Ignitor Gas MV Flame Sensor Blower Motor Humidifier 120V Humidif...

Page 5: ...mately 2 seconds or until the LED turns off Release the switch and the LED will remain off for 2 seconds Fault codes will display beginning with the most recent fault first with a 2 second pause betwe...

Page 6: ...correct 8 Recycle External Lockout See Troubleshooting comments for Retry External Lockout 9 Reversed 120 VAC Line Polarity or Bad Ground Verify the control and furnace is properly grounded Check and...

Page 7: ...erminal 120 VAC FAN 1 4 spade terminal OUTPUT circulator blower FAN SPEED terminal 120 VAC PARK 3 terminals 1 4 spade terminal Unused circulator blower terminals N A LINE H 1 4 spade terminal INPUT Li...

Page 8: ...gas supply 2 sec Recycles N A The additional attempts within the same thermostat cycle for ignition after loss of the supervised ignition source or the supervised main burner flame 5 attempts Retries...

Page 9: ...emplace 37 7616A 1620 Contr le de fournaise int gr e 50M56 801 2 faisceaux de fils tiquette de la commande Attache pour fils Directives d installation Sp cifications lectriques 77 F 25 C Tension d ent...

Page 10: ...les autres branchements 74W03 103098 01 1195 100 1195 83 100A Respecter les directives d installation ou d entretien recommand es par le fabricant de l appareil pour assurer un fonctionnement appropri...

Page 11: ...120 V 120 V Allumeur 120 V c a TRANSFORMATEUR CLASSE II 24 V c a 24 V c a TH TR D lai fermeture clim 60 s 2 s D lai marche chauf 45 s 30 s 60 s 120 s 90 s 180 s SW1 SW1 SW1 SW1 SW1 SW1 ARR T ARR T ARR...

Page 12: ...u point de r glage du thermostat Post purge 25 secondes D lai de mise l arr t du ventilateur 60 90 120 180 secondes Syst me l arr t Thermostat Inducteur Pressostat Allumeur Gaz mV Capteur de flamme Mo...

Page 13: ...2 secondes ou jusqu ce que la DEL s teigne D clencher le commutateur et la DEL reste teinte pendant 2 secondes Les codes d erreur s affichent alors en commen ant par l erreur la plus r cente suivie d...

Page 14: ...age dans la section Essayer de nouveau Verrouillage externe 9 Polarit de ligne 120 V c a invers e ou mauvaise prise de terre S assurer que le module de commande et la fournaise sont correctement mis l...

Page 15: ...120 V c a VENT Borne embrochable de 1 4 po SORTIE Borne VITESSE DE CHAUFFAGE du ventilateur de circulateur 120 V c a PARC 3 bornes Borne embrochable de 1 4 po Bornes du ventilateur de circulateur non...

Page 16: ...ource d allumage supervis e ou de la flamme supervis e du br leur principal 5 essais R essais S O Les essais successifs l int rieur du m me cycle d allumage du thermostat lorsque la flamme supervis e...

Reviews: