TROUBLE SHOOTING
30
January 2009 / W-SQ16 for mobile applications / EN
PROBLEM CAUSE
SOLUTION
•
Insufficient intake air.
•
Choked air filter.
Check intake air paths and filter, clean and
replace if necessary.
•
Fuel injector faulty.
Replace injector.
•
Valve clearance incorrect.
Readjust valve clearance
•
Poor fuel quality.
Use better quality diesel.
•
Poor quality lubricating oil.
Use better quality oil.
•
Continuous running with very low load.
Increase load up to 70% of nominal power and
have the engine run for a few hours
Loss of power
●
Wrong measurement. Check if the load is measured correctly. Does the Amp meter show
the correct value? When calculating the load by multiplying voltage and amps this should be
done by using the exact values, taking into account the power factor of the consumers. When
any doubt, measure the power directly with an appropriate instrument.
•
Overfull oil sump.
Bring the oil to the correct level
•
Choked fuel filter.
Replace the fuel filter.
•
Choked air filter.
Check air inlet openings; clean air filter.
•
Exhaust blocked.
Check the exhaust system.
•
Faulty fuel pump
Check and replace if nescessary
•
Injector blocked.
Have the injector checked.
•
Loss of compression, sticking or
damaged piston ring.
Have the compression measured.
Clean or replace the rings.
•
Wear out of cylinder.
Have the compression measured and have the
engine overhauled.
Over-temperature
•
Overload.
Take away the overload.
•
Low level of coolant or air in the
cooling system
Fill up with coolant and release air bubbles.
Check if there are air blocks in the system; refer
to the installation manual
•
Broken impeller.
•
Radiator choked by dirt
•
Hot air circulation in radiator.
Check the cooling system thoroughly.
Clean radiator
•
Broken or slipping V-belt.
Replace and adjust the V-belt tension.
•
Faulty thermostat
Check the thermostat or replace.
5.2.3 Warnings
Generator must be shut off immediately if:
●
Motor RPM suddenly rises or drops.
●
Unusual noise comes from generating set.
●
Exhaust gases suddenly colour dark.
●
Engine failure warning light is on
5.2.4 Service
address
If you cannot correct a problem with the aid of the mal-
function table, contact your Whisper Power Service Centre
or Whisper Power Netherlands for an extended service
list, tel: INT +31-512-571550.