Set 1. Press the “Set” button once and it will display the set point. After approximately 5 seconds,
the display will return to normal operation and display the bottle probe temperature.
2. Press the “Set” button once and it will display the set point. Press the “UP” and “DOWN”
arrows to change the set point. Press the “Set” button again and the numbers will blink,
confirming the change in set point.
3. Press and hold the “Set” button during the display of the Hi/Low “Temperature Data
History” (hold button unit “rst” blinks on display), and it will erase the past recorded data
file and start recording from the current time and temperature.
4. Press the “Set” and the “DOWN” buttons simultaneously, for
3-5 seconds
, and you will
access the “Customer Preference Selection Mode” (CPSM). The CPSM allows the customer
to fine-tune the Control Operating System to their applicable choice.
Alarm The Alarm symbol is shown when the unit encounters an issue that needs attention.
The displayed alarm codes are explained below.
Alarm Codes
Message
Cause
Solution
“P1”
Bottle probe is unplugged
Attach bottle probe to unit
Faulty bottle probe connection
1. Check bottle probe attachment at circular connector.
2. Check bottle probe connection at green terminal block on the
controller
Defective bottle probe
Replace the bottle probe
“P2”
Faulty evaporator probe
connection
Check evaporator probe connection at green terminal block on the
controller
Defective evaporator probe
Replace the evaporator probe
“HA”
Defective bottle probe
Replace the bottle probe
“LA”
The bottle probe is sensing a
temperature of 4° below the
set point
Allow the room to warm up. This will increase the temperature of the
wine
Defective bottle probe
Replace the bottle probe
“POF”
The keypad is locked
Hold “UP” and “DOWN” arrows for 3 to 5 seconds to disable, “PON”
should appear
“BAL”
Unit is not draining properly
1. Check to see if the drain tube is clogged.
2. Check to see if the float is working correctly.
Summary of Contents for Quantum SS12000
Page 20: ...Page 18 1 800 343 9463 QS 021616 QUANTUM SS9000 CONDENSER WIRING DIAGRAM ...
Page 21: ...www whisperkool com Page 19 QUANTUM SS12000 CONDENSER WIRING DIAGRAM ...
Page 31: ...www whisperkool com Page 29 NOTES ...
Page 40: ...QS 021616 WhisperKOOL 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www whisperkool com ...