9.5 Cooling capacity for 15Ton:
Air Flow
(
CFM
)
5400
6000
6600
7200
Ent
(
DB
)
(
o
F
)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
Am
bien
t Temp
er
atur
e
85
61
TGC
157.1 159.1 166.4 176.2 161.5 165.1 172.5 182.2 163.4 167.7 178.6 187.1 170.1 172.5 182.3 189.6
SHC
125.0 149.3 159.5 168.8 132.2 159.1 167.1 176.5 139.6 160.7 171.2 179.4 145.8 165.3 174.8 181.7
67
TGC
176.8 179.0 181.1 183.7 182.2 183.5 184.6 185.9 184.5 186.0 187.1 188.6 186.0 187.1 189.6 190.8
SHC
98.2 121.3 143.3 166.4 102.8 126.2 150.6 173.7 104.7 129.9 155.5 181.1 107.2 133.6 160.3 187.1
73
TGC
187.1 190.8 193.3 195.7 189.3 192.0 195.7 198.0 191.8 194.5 196.8 199.3 194.5 197.7 200.1 202.6
SHC
65.7
90.3 110.5 129.9
67.1
92.5 113.1 132.1
68.4
93.4 115.1 137.2
69.6
94.5 116.6 141.1
95
61
TGC
146.9 150.6 158.0 168.9 148.8 155.5 165.2 174.9 154.3 158.0 170.1 179.8 158.0 164.0 174.9 183.5
SHC
118.8 143.3 153.0 163.6 126.2 150.6 160.1 169.5 133.6 153.0 164.8 174.3 139.6 158.9 169.5 177.8
67
TGC
165.2 167.7 170.1 173.7 172.5 173.5 176.2 177.4 178.6 180.0 181.2 182.2 179.2 181.7 183.3 191.4
SHC
93.4 116.5 139.6 162.7
97.6 122.5 147.0 172.5 101.6 126.3 154.3 179.8 104.6 132.4 160.3 182.4
73
TGC
182.3 184.6 187.0 189.6 183.7 185.7 188.7 192.0 185.4 187.8 190.3 191.5 189.1 192.8 195.2 197.7
SHC
62.5
86.6 108.3 128.7
64.0
89.8 111.3 133.6
65.3
91.4 114.2 137.2
66.7
93.0 116.5 140.9
105
61
TGC
136.2 139.9 147.3 159.6 141.1 144.8 157.1 164.5 143.6 149.7 163.2 172.1 147.3 155.9 168.2 178.0
SHC
113.1 134.0 141.1 152.9 121.4 138.7 150.5 157.6 128.8 145.0 158.1 166.7 133.6 151.0 162.9 172.5
67
TGC
157.1 159.6 163.2 164.5 158.3 162.0 166.9 169.4 166.9 169.4 171.9 174.3 170.6 173.1 175.5 180.0
SHC
88.1 111.6 134.8 159.2 102.5 117.7 143.3 164.1
96.1 123.8 150.6 168.9
99.8 128.7 158.0 178.0
73
TGC
179.2 180.5 181.7 182.9 181.7 182.9 184.2 186.6 184.2 185.4 186.6 187.8 185.4 186.6 187.8 190.3
SHC
59.1
82.7 105.2 126.3
60.5
85.8 109.0 132.4
61.8
88.8 112.1 135.9
63.1
90.1 115.0 142.3
115
61
TGC
123.9 128.8 141.1 153.4 127.6 135.0 147.3 159.6 131.3 133.9 144.4 165.7 135.0 144.8 158.3 169.4
SHC
108.0 124.7 136.7 148.6 115.1 129.3 141.1 152.9 121.4 129.7 139.9 160.5 120.8 140.3 153.4 164.1
67
TGC
147.3 149.7 150.9 154.4 148.5 152.2 154.6 157.1 157.1 159.6 163.2 167.5 160.8 163.2 165.7 169.4
SHC
91.9 106.9 130.0 153.4
96.8 113.4 138.6 157.1 101.7 119.0 144.8 162.3
95.3 125.1 154.6 165.9
73
TGC
166.9 169.4 171.9 173.1 171.9 174.3 175.5 176.8 175.5 176.8 178.0 179.2 176.8 178.0 179.2 180.5
SHC
55.6
79.1 102.4 125.1
57.0
83.3 106.7 130.0
59.9
85.8 111.6 137.4
59.9
89.4 114.0 139.9
125
61
TGC
118.9 123.6 135.4 145.6 122.4 129.5 141.3 153.2 126.0 134.2 147.3 159.1 129.5 139.0 152.0 162.6
SHC
103.6 119.7 131.2 141.0 110.5 125.4 136.9 148.4 116.5 130.0 142.6 154.1 115.9 133.2 145.6 155.9
67
TGC
141.3 143.7 144.9 147.3 142.5 146.1 148.4 150.8 150.8 153.2 156.7 160.6 154.3 156.7 159.1 164.6
SHC
88.1 102.5 124.8 147.3
92.8 108.8 133.1 146.1
97.6 114.1 139.0 155.6
91.4 120.0 148.4 159.5
73
TGC
160.3 162.6 165.0 166.2 165.0 167.4 168.5 169.7 168.5 169.7 170.9 172.1 169.7 170.9 172.1 173.3
SHC
53.2
75.8
98.2 120.0
54.5
79.8 102.3 124.8
57.4
82.2 107.0 131.9
57.4
85.8 109.4 134.2
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: 1000Btu/h).
3. SHC=Sensible Heat Capacity. (Unit: 1000Btu/h).
Heating capacity for 15Ton:
Net Capacities(kW)-6000 CFM
Outdoor Temp
(
℉
)
70% RH
Peak Net Heating(kW) at Indicated Dry Bulb
(
℉
)
Peak Total Power(KW) at Indicated Dry Bulb
(
℉
)
59 68 75.2
80.6
59
68 75.2
80.8
5
29.7
27.9
27.3
26.9
13.8
15.2
16.1
17.0
10.4
32.0
30.6
30.0
29.7
14.1
15.5
16.2
17.3
15.8
33.9
33.0
32.7
32.7
14.3
15.6
16.4
17.6
21.2
35.6
34.5
34.2
33.8
14.4
15.8
16.7
17.9
26.6
37.7
37.1
36.8
36.2
14.6
15.9
17.0
18.2
32
40.5
39.9
39.3
38.9
14.7
16.2
17.3
18.3
37.4
46.7
46.2
45.5
44.9
15.0
16.5
17.6
18.6
44.6
56.7
56
54.3
53.7
15.6
17.5
18.2
19.2
48.2
61.1
60.3
59.7
59.1
16.2
18.0
19.1
20.3
53.6
64.8
67.1
66.8
66.2
16.8
18.8
19.8
21.0
59
69.9
68.9
68.4
67.7
17.3
19.2
20.3
21.5
64.4
74.1
72.8
72.0
71.4
17.7
19.7
20.9
21.9
69.8
79.5
77.9
76.8
75.8
18.0
20.0
21.0
22.1
75.2
84.0
81.8
80.4
79.5
18.5
20.3
21.8
22.5
Notes:
1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
Summary of Contents for WPAPH-090CA4
Page 1: ...ROOFTOP PACKAGE A C SERVICE MANUAL R 410A 220VOLTS 60HZ...
Page 19: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 18 7 2 7 5ton...
Page 20: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 19 7 3 10 ton...
Page 22: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 21 7 5 15 17 5ton...
Page 23: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 22 7 6 20 ton...
Page 42: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 41 10 Explode View WPAXH 060CA4...
Page 45: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 44 WPAXH 090CA4...
Page 52: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 51 WPAXH 120CA4...
Page 59: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 58 WPAXH 150CA4...
Page 62: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 61 WPAXH 180CA4...
Page 65: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 64 WPAPH 180CA4...
Page 69: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 68 WPAXH 205CA4...
Page 75: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 74 WPAPH 240CA4...
Page 94: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 93 Typical rooftop application with frame...