9. Performance Data
9.1 Cooling capacity for 5Ton:
Ambie
nt
Temperat
ure
(
℉
)
Air Flow
CFM
1800
Ent DB
(
℉
)
75 80 85 90
75
E
n
te
rin
g W
et
B
ul
b(
℉
)
61
TGC 63.6 66.8 72.8 75
SHC 46.8 48.1 51.7 53.2
67
TGC 65.7 69 74.5 76.7
SHC 47.3 49 52.9 54.5
73
TGC 67.4 70.7 76.4 78.3
SHC 47.8 50.2 54.2 55.7
85
61
TGC 59.6 62.6 68.2 70.3
SHC 42.9 45.1 49.1 50.6
67
TGC 61.5 64.6 69.7 71.8
SHC 44.3 46.5 50.2 51.7
73
TGC 63 66.2 71.5 73.3
SHC 45.4 47.7 51.5 52.8
95
61
TGC 55.5 58.3 63 64.8
SHC 41.1 43.1 46.6 48
67
TGC 57.1 60 65 66.9
SHC 41.7 44 47.2 48.8
73
TGC 58.7 61.7 66.6 68.3
SHC 42.9 45 48.6 49.8
105
61
TGC 51.6 54.2 59 60.8
SHC 39.7 41.7 45.5 46.8
67
TGC 53.2 55.9 60.3 62.2
SHC 40.4 42.5 45.9 47.2
73
TGC 54.6 57.3 61.9 63.4
SHC 40.9 43 46.4 47.6
115
61
TGC 47.4 49.7 54.2 55.8
SHC 38.8 39.3 42.8 44.1
67
TGC 48.8 51.2 55.7 57.4
SHC 39 39.8 43.7 45.4
73
TGC 49.9 52.4 57.1 58.6
SHC 39.4 41.4 45.1 46.2
Notes:
1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit:1000Btu/h).
3. SHC=Sensible Heat Capacity. (Unit: 1000Btu/h).
Summary of Contents for WPAPH-090CA4
Page 1: ...ROOFTOP PACKAGE A C SERVICE MANUAL R 410A 220VOLTS 60HZ...
Page 19: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 18 7 2 7 5ton...
Page 20: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 19 7 3 10 ton...
Page 22: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 21 7 5 15 17 5ton...
Page 23: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 22 7 6 20 ton...
Page 42: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 41 10 Explode View WPAXH 060CA4...
Page 45: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 44 WPAXH 090CA4...
Page 52: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 51 WPAXH 120CA4...
Page 59: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 58 WPAXH 150CA4...
Page 62: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 61 WPAXH 180CA4...
Page 65: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 64 WPAPH 180CA4...
Page 69: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 68 WPAXH 205CA4...
Page 75: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 74 WPAPH 240CA4...
Page 94: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 93 Typical rooftop application with frame...