![Westinghouse WPAPH-090CA4 Service Manual Download Page 106](http://html1.mh-extra.com/html/westinghouse/wpaph-090ca4/wpaph-090ca4_service-manual_964289106.webp)
WESTINGHOUSE PACKAGE A/C MANUAL
R-410A : 220V: 60Hz
105
17.2 Trouble shooting
For 5ton
Item Content Error
code
1
Compressor phase sequence error or phase default
E0
2
Outdoor coil temp. sensor T3-1 default
E1
3
Outdoor coil temp. sensor T3-2 default
E2
4
Indoor coil temp. sensor T2-1 default
E5
5
Indoor coil temp. sensor T2-2 default
E6
6
Indoor temp. sensor T1 error
E9
7
Outdoor ambient temp. sensor T4 error
EA
8
Wired controller output error
Eb
9
Over current protection
P0
10
Comprehensive protection for outdoor fan
P3
11
Protection for High/Low Pressure or exhaust temp.
P4
1) E0
:
Compressor phase sequence error or phase default
2) E1
:
Outdoor coil temp. sensor T3 default.
Yes
No
Yes
Yes
No
No
Detect if the temp. Sensor is normal.
Cut off power supply, replace the
power wire, inspect again.
Detect if the voltage of 5p wire joint
between A, B and C is normal.
Cut off power supply, exchange
freely two wires between A, B and
C. Power on again, if the main
board display E0.
Detect if the main board voltage
between A, B and C is normal.
Cut off power supply, exchange the
wire from main power supply to main
board. Power on again, retesting.
Replace the main board.
OK.
Replace the main board.
Yes
No
Replace the temp. sensor, detect
it again.
Summary of Contents for WPAPH-090CA4
Page 1: ...ROOFTOP PACKAGE A C SERVICE MANUAL R 410A 220VOLTS 60HZ...
Page 19: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 18 7 2 7 5ton...
Page 20: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 19 7 3 10 ton...
Page 22: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 21 7 5 15 17 5ton...
Page 23: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 22 7 6 20 ton...
Page 42: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 41 10 Explode View WPAXH 060CA4...
Page 45: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 44 WPAXH 090CA4...
Page 52: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 51 WPAXH 120CA4...
Page 59: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 58 WPAXH 150CA4...
Page 62: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 61 WPAXH 180CA4...
Page 65: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 64 WPAPH 180CA4...
Page 69: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 68 WPAXH 205CA4...
Page 75: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 74 WPAPH 240CA4...
Page 94: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 93 Typical rooftop application with frame...