5) Outdoor fan motor didn’t run.
6) Four ways valve didn’t work.
No
Yes
Yes
No
Yes
Yes No
Yes
No
Yes
No
Yes
No
No
No
Detect if the voltage of compressor which
corresponds to the interface on PCB is 208 ~ 230V
AC between CN6 of OFAN1,OFAN2 and N.
Replace
transformer.
Detect if the fuse on PCB is burned off.
If the outdoor fan motor contactor is
close.
Replace outdoor
fan motor.
Replace
contactor.
Replace
fuse.
Check if the secondary voltage
transformer is normal.
Replace PCB.
Replace
transformer.
Detect if the voltage is 208 ~ 230V AC
between CN28, CN29 and C on PCB.
Replace four way valve or coil.
Detect if the fuse on PCB is burned off.
Check if the secondary voltage
transformer is normal.
Replace
fuse.
Replace
PCB.
Summary of Contents for WPAPH-090CA4
Page 1: ...ROOFTOP PACKAGE A C SERVICE MANUAL R 410A 220VOLTS 60HZ...
Page 19: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 18 7 2 7 5ton...
Page 20: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 19 7 3 10 ton...
Page 22: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 21 7 5 15 17 5ton...
Page 23: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 22 7 6 20 ton...
Page 42: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 41 10 Explode View WPAXH 060CA4...
Page 45: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 44 WPAXH 090CA4...
Page 52: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 51 WPAXH 120CA4...
Page 59: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 58 WPAXH 150CA4...
Page 62: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 61 WPAXH 180CA4...
Page 65: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 64 WPAPH 180CA4...
Page 69: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 68 WPAXH 205CA4...
Page 75: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 74 WPAPH 240CA4...
Page 94: ...WESTINGHOUSE PACKAGE A C MANUAL R 410A 220V 60Hz 93 Typical rooftop application with frame...