Westinghouse WGR050NG076 Installation, Start-Up, Maintenance, Parts, Warranty Download Page 19

WHL-001 Rev. 001 Rel. 008 Date 8.23.18

19

E. Exhaust Vent and Intake Pipe Sizing

1. The exhaust vent and intake pipe size is 2”.

2. The total equivalent length of exhaust vent and intake pipe 

should not exceed 150 feet

.

a. The equivalent length of elbows, tees, and other fittings are 

listed in the Friction Loss Table.

Friction Loss Equivalent in Piping and Fittings

Fittings or Piping

Equivalent Feet

2”

3”

90 Degree Elbow*

5’

5’

45 Degree Elbow

3’

3’

Coupling

0’

0’

Air Inlet Tee

0’

0’

Straight Pipe

1’

1’

Concentric Kit

3’

3’

V500 2” Kit

1’

N/A

V1000 3” Kit

N/A

1’

V2000 4” Kit

N/A

1’

Table 7 - *Friction loss for long radius elbow is 1 foot less. NOTE: Consult 

Polypropylene venting instructions for friction loss and pressure drop 

equivalents.

b. For example: If the exhaust vent has two 90

o

 elbows and 10 

feet of PVC pipe we will calculate:

Exhaust Vent Equivalent Length = (2x5) + 10 = 20 feet.

Further, if the intake pipe has two 90

o

 elbows, one 45

o

 elbow, 

and 10 feet of PVC pipe, the following calculation applies:

Intake Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet.

Finally, if a concentric kit is used we find:

Total Equivalent Length = 20 + 23 + 3 = 46 feet.

The total equivalent length is 46 feet, well below the maximum 

of 150 feet.

c. Effort should be made to keep a minimum difference in 

equivalent length between the exhaust vent and intake pipe.

3. The minimum total equivalent length is 16 feet.

Do not exceed the maximum lengths for vent pipes. Excessive 

length could result in heater shutdown and property damage.
Failure to provide a minimum total vent length of 16 equivalent 

feet could result in property damage and improper product 

operation.

F. Longer Vent Runs

The maximum total equivalent length can be extended by increasing 

the diameter of both the exhaust vent and intake pipes. However, 

the transitions should begin a minimum of 15 equivalent feet from 

the water heater.

a. 

The maximum total equivalent length for increased 

diameter vent pipes is 200 feet.

b. Transitions should always be made in vertical sections of pipe 

to prevent the condensate from pooling in the vent pipe. 

Vent Connection

Reducing Coupling

Vent Transition

2”

3” x 2”

3”

Table 8 - Vent Run Transition

c. Transition from 2” to 3” pipe should be made at the water 

heater. 

G. Exhaust Vent and Intake Pipe Installation

All joints of positive pressure vent systems must be sealed completely 

to prevent leakage of flue products into the living space. Failure to 

do so could result in property damage, serious injury, or death.

1. Use only solid PVC or CPVC pipe or a Polypropylene vent system 

approved for use with Category IV appliances.

FOAM CORE PIPING IS NOT APPROVED FOR EXHAUST VENT 

APPLICATIONS. Foam core piping may be used on air inlet piping 

only

.

2. Remove all burrs and debris from joints and fittings.

3. When using PVC or CPVC pipe, all joints must be properly cleaned, 

primed, and cemented. Use only cement and primer approved for 

use with the pipe material. Cement must conform to ASTM D2564 

for PVC and ASTM F493 for CPVC pipe. 

NOTE: DO NOT CEMENT 

POLYPROPYLENE PIPE.

4. Ensure the vent is located where it will not be exposed to prevailing 

winds.

5. In all roof venting applications, exhaust discharge must point away 

from the pitch of the roof.

6. To prevent water leakage, install adequate roof flashing where the 

pipe enters the roof.

7. Do not locate vent over public walkways, driveways, or parking lots. 

Condensate could drip and freeze, resulting in a slip hazard or damage 

to vehicles and machinery.

8. Due to potential moisture build-up, sidewall venting may not be 

the preferred venting option. To save time and cost, carefully consider 

venting installation and location.

9. Horizontal lengths of exhaust vent must slope back towards the 

water heater not less than ¼” per foot to allow condensate to drain 

from the vent pipe.

10. The exhaust vent must terminate where vapors cannot make 

accidental contact with people or pets, or damage shrubs or plants.

11. In vacant chimney applications, install and seal a rain cap over 

existing chimney openings.

12. All piping must be fully supported. Use pipe hangers at a minimum 

of 4 foot intervals to prevent sagging of the pipe where condensate 

may form.

13. Do not use the heater to support any piping.

14. A screened straight coupling is provided with the heater for use as 

an outside exhaust termination.

15. A screened inlet air tee is provided with the heater to be used as 

an outside intake termination.

16. Maximum Snow Level Determination: These installation 

instructions reference snow levels in establishing a minimum height 

for the installation of exhaust vent or air intake terminations. Snow 

levels shall be determined as follows:  

a. The installation location may, by ordinance, designate how snow 

levels are calculated in that location; or

b. In the absence of specific ordinances, snow levels shall be calculated 

from the average monthly maximum depth of snow accumulation as 

indicated by the National Weather Service’s 10 year statistics for the 

installation location/geographical area.

In addition:

• 

Total length of vent piping shall not exceed the limits specified 

in this manual.

• 

The vent piping for this direct vented appliance is approved for 

zero clearance to combustible construction.

• 

The flue products coming from the exhaust vent will create a 

large plume when the heater is in operation. Avoid venting in 

areas that will affect neighboring buildings or be considered 

objectionable.

• 

DO NOT locate exhaust vent or intake pipe in a parking area 

where machinery may damage the pipe.

Summary of Contents for WGR050NG076

Page 1: ...ce and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE www westinghousewaterheating com WHL 001 Rev 001 Rel 008 Date 8...

Page 2: ...e Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your ga...

Page 3: ...stalledbyqualifiedandlicensedpersonnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements In the absence of local co...

Page 4: ...repare the Water Heater 6 A Locating the Water Heater 7 B Leveling 7 C Clearances for Service Access 8 D Residential Garage and Closet Installations 8 E Exhaust Vent and Intake Pipe 8 1 Direct Vent of...

Page 5: ...to heat potable water ONLY Using this water heater to heat non potable fluid WILL VOID product warranty and could result in property damage personal injury or death Do not use this water heater for an...

Page 6: ...ature and adjusts fan speed to regulate the heater s energy output This allows the unit to deliver the required amount of heated energy and nothing more Burner Constructed of high grade stainless stee...

Page 7: ...m air for combustion Indoor air will have a much lower relative humidity and hence potential corrosion will be minimized High heat sources generating heat 100o F 37o C or greater such as boiler flue p...

Page 8: ...ould result in severe personal injury or death Do not attempt to vent this water heater by any means other than those described in this manual Doing so will void the warranty and may result in severe...

Page 9: ...inch per 1 000 BTU hr 22cm2 kW of the total input of all appliances in the space but not less than 100 square inches 645cm2 If the confined space is within a building of tight construction air for co...

Page 10: ...ith EPA secondary maximum contaminant levels 40 CFR Part 143 3 If the water contains contaminants higher than outlined by the EPA water treatment is recommended and additional more frequent maintenanc...

Page 11: ...se as required by ANSI Part 4 Piping Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage severe personal injury or death DO NOT pipe this water...

Page 12: ...The expansion tank must be located as shown in Applications this manual or following recognized design methods See expansion tank manufacturer s instructions for details Use a backflow preventer spec...

Page 13: ...nt temperature as low as possible Feel water before bathing or showering If thermostatic valves are required use devices specifically designed for such purpose Install these devices in accordancewithi...

Page 14: ...r all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scaldin...

Page 15: ...ithout water will result in dry firing NOTES FOR AIR HANDLER APPLICATION 1 MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AI...

Page 16: ...state provincial and national codes for best practices to prevent condensate freezing in the exhaust vent pipe system Improper seating of vent pipe gaskets can cause eventual gasket failure and exhau...

Page 17: ...p terminations clear could result in property damage severe personal injury or death The exhaust and intake components installed with this water heater must be used for near water heater piping BEFORE...

Page 18: ...t may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit locate...

Page 19: ...piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use only cemen...

Page 20: ...ree feet for concealed piping b At all changes of direction c On each side of a penetration through a partition wall or ceiling and d The labels shall be black lettering that i Indicates that the pipi...

Page 21: ...ing support brackets on vent piping the first bracket must be within 1 foot of the water heater and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Page 22: ...IDE VIEW LP 325 PP EXHAUST AIR INTAKE F E D C EXHAUST AIR INTAKE B Figure 10 Horizontal Snorkel Venting UNBALANCED VENTING WITH TEE INTAKE AND COUPLING EXHAUST All vent pipes must be glued properly su...

Page 23: ...er to Concentric Vent Kit installation manual LP 166 for further information on venting with the optional concentric vent kits Concentric venting through an existing system must run vertically through...

Page 24: ...sidered part of the space Confined space is space with volume less than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of all fuel burning appliances installed in t...

Page 25: ...cidic pH from 3 2 to 4 5 Install a neutralizing filter if required by local codes Power to the optional condensate pump is continuous When the water heater is powered off the condensate pump will rema...

Page 26: ...WHL 001 Rev 001 Rel 008 Date 8 23 18 26 1 2 3 4 Figure 16 Removing and Installing the Condensate Neutralizer Water Heaters Manufactured Prior to 9 27 17 ONLY...

Page 27: ...uctions are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building It is preferable to mount the sensor on the north side in an area that will not be af...

Page 28: ...ing plate LP for liquefied petroleum propane gas or Nat for natural or city gas All gas connections must be approved by the local gas supplier or utility in addition to the governing authority prior t...

Page 29: ...being installed If there are additional gas appliances on the main supply line size the supply line for the maximum total COMBINED BTU Hr draw of the appliances This will ensure the supply line is siz...

Page 30: ...ts individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at pressures greater than psi 3 5 kPa 2 The water heater must be isolated f...

Page 31: ...t in increments of two degrees After choosing the setpoint wait five seconds The screen will return to normal operation and the setpoint will be stored 70 160 120 Outdoor Reset Curve Enabling Outdoor...

Page 32: ...sume water heater operation 3 Putting the Water Heater in ECO Mode Press to put the water heater in ECO Mode Press to resume normal operation 4 Changing User Setpoint Press either or once to change th...

Page 33: ...imum tank temperature for reset curve 70 160 140 P10 Warm Weather Shutdown Temperature o C o F Outdoor temperatures greater than this value return the tank target temperature to the User Setpoint 50 1...

Page 34: ...een cleared Press at any History Mode screens to return to the upper level menu Part 10 Start Up Procedure FOR YOUR OWN SAFETY READ BEFORE OPERATING 1 This water heater does not have a pilot It is equ...

Page 35: ...a maximum of 15 minutes 8 Test Mode can be disabled by pressing Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2...

Page 36: ...result in property damage serious personal injury or death Such damages ARE NOT covered by water heater warranty Part 12 Troubleshooting A Error Code An error code may occur during installation of th...

Page 37: ...the sensor is 40o F 122o F 2 Check the Outdoor Temperature Sensor Ensure it is properly wired and connected and that there are no breaks cuts or other visible issues with the sensor wire 3 Use an ohm...

Page 38: ...ault code occurs again reset the water heater and 3 When water heater attempts to fire check voltage at the gas valve connector If there is voltage but no gas pressure on the outlet side of the valve...

Page 39: ...serve water heater operation If fault code occurs again 3 Check the Dual Temperature Sensor Ensure it is properly wired to the control and that there are no breaks cuts or other visible issues with th...

Page 40: ...ons been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust ven...

Page 41: ...ter that has not been used for a long period of time generally two weeks or more When opening a hot water faucet in a system that has been out of use for a time keep all ignition sources electrical ap...

Page 42: ...ctrode Clean Set gap at 1 4 Clean probe with plumbers cloth to remove oxides Combination Ignitor and Flame Probe Check ionization in uA i04 in the Inquiry Mode menu Record high fire and low fire Clean...

Page 43: ...T P A D A 4 8 6 0 P 0 0 7 7 S P M A L C w E S O H E T A S N E D N O C 5 4 4 0 P 0 0 1 7 B R A B X E L A M T P N 2 1 G N I T T I F 6 2 0 0 P 0 0 7 7 2 1 T U N K C O L 7 7 7 0 P 0 0 7 7 2 1 X 2 1 R E T...

Page 44: ...00P 004 27 CONDENSATE HOSE w CLAMPS 7700P 068 28 FITTING 1 2 NPT MALE X BARB 7100P 044 29 LOCKNUT 1 2 7700P 002 30 ADAPTER 1 2 X 1 2 7700P 077 31 FLUE TEMPERATURE SENSOR 7450P 026 32 PRESSURE SWITCH 7...

Page 45: ...t s E If at the time of a request for service the Owner cannot provide a copy of the original sales receipt or the warranty registration the warranty period for the water heater shall then be deemed t...

Page 46: ...warranty registration for a warranty service request If the water heater is in warranty contact the retailer from whom the water heater was purchased or the installer for assistance Be prepared to pro...

Page 47: ...WHL 001 Rev 001 Rel 008 Date 8 23 18 47 Maintenance Notes...

Page 48: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Reviews: