Westinghouse WEC080C2X030 Use And Care Manual Download Page 8

whl-035 Rev. 002 Rel. 002 Date 11.1.17

8

B. Thermal Expansion

Dielectric unions or galvanized steel fittings must not be used in a 

system with this water heater. Doing so WILL VOID the warranty. It 

is recommended to use only copper, brass, or stainless steel fittings. 

Teflon thread sealant must be used on all connections.

1. Install a shut-off  or check valve or both on the inlet connection on 

the top of the heater. Connect the cold water supply line to the shut-

off valve or check valve. Refer to piping Applications, this manual.

Do not apply heat to the Hot or Cold water heater connections. If 

sweat connections are used, sweat tubing to the adapter before 

fitting adapter to the water connections on the heater. Any heat 

applied to the water heater connections will permanently damage 

the dip tube and/or heat traps. Damages due to improper installation 

practices ARE NOT covered by warranty.

2. Connect the hot water line to the connection marked “HOT” on the 

top of the water heater.

3. Install the T&P Valve in the opening provided near the top of the 

heater.

4. Install drain valve in the opening provided near the bottom of the 

heater.

A check valve may be installed in the cold water inlet line as a separate 

backflow preventer, or may be part of a pressure reducing valve, water 

meter, or water softener. An “

open water system

” refers to a system 

without a check valve. A “

closed water system

” refers to a system with 

a check valve installed in the cold water inlet line.

As water is heated, it expands in volume and increases pressure within 

the water system. This action is referred to as “

thermal expansion

”. In 

an open water system, expanding water which exceeds the capacity 

of the system flows back into the city main where pressure is easily 

dissipated.

A closed water system prevents expanding water from flowing back 

to the city main. The resulting thermal expansion can rapidly increase 

pressure in the water heater and system piping. This rapid pressure 

increase can exceed the setting of the pressure relief valve, causing it to 

operate during each heating cycle, resulting in discharge from the T&P. 

This rapid and repeated expansion and contraction of components 

in the system can cause premature failure of system components, 

including the relief valve and possibly the water heater. Replacing the 

relief valve 

will not 

correct thermal expansion.

A potable hot water expansion tank is required to offset thermal 

expansion. Expansion tanks are designed with an air cushion built 

in that compresses as system pressure increases, thereby relieving 

the overpressure condition and eliminating repeated operation of 

the relief valve. This expansion tank should be installed in the cold 

water line between the water heater and check valve, and must be 

sized for the entire water volume of the hot water system. See piping 

Applications.

Other methods of controlling thermal expansion are available. 

Check 

with the local water utility to determine if a check valve exists in 

A. Plumbing

It is mandatory that all plumbing be done in accordance with federal, 

local, and state plumbing codes and practices. Failure to properly 

install the water heater WILL VOID the warranty. It is also necessary to 

use both thread tape and pipe sealing compound on all mechanical 

plumbing connections.

It is recommended to use unions on the hot and cold water connections 

to easily disconnect the water heater for servicing.

Part 3 - Piping

the cold water inlet line.

 Contact your installing contractor, water 

supplier, or plumbing inspector for additional information regarding 

thermal expansion.

C. Condensation

Condensation can form on the water heater when it is first filled with 

water, and may also occur with a heavy water draw and very cold inlet 

water temperature. This condition is not unusual and will disappear 

as the water becomes heated. However, if the condensation should 

continue, examine the piping and fittings for possible leaks.

D. Insulation Blankets

If local codes require external application of insulation blanket 

kits, the manufacturer’s instructions included with the kit must be 

carefully followed.

In addition, pay careful attention to the following so as not to 

restrict the proper function and operation of the water heater:

• 

Do not cover the operating or warning labels attached to 

the water heater or attempt to locate them on the exterior 

of the insulation blanket.

• 

Do not apply insulation to the top of the water heater. This 

could interfere with the safe operation of the electrical 

junction box.

• 

Do not cover the jacket access panel(s) to the thermostat(s) 

and heating element(s) or T&P valve.

• 

Inspect the insulation blanket frequently.

Failure to follow these instructions could result in property damage, 

severe personal injury, or death.

E. Temperature and Pressure Relief Valve

For protection against excessive pressures and temperatures in this 

water heater, install temperature and pressure protective equipment 

as required by local codes, but not less than a  combination T&P 

valve meeting the requirements for 

Relief Valves and Automatic Gas 

Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22B / CSA 4.4-

M99

 by a nationally recognized testing laboratory that maintains 

periodic inspection of production listed equipment and materials. 

This valve must be marked with a maximum set pressure not to 

exceed the marked maximum working pressure of the water heater. 

Install the T&P valve into the opening provided and marked for this 

purpose on the water heater. The T&P valve must be plumbed down 

so discharge can exit at least 6” above the structural floor. The relief 

line cannot be in contact with any live electrical parts.

Summary of Contents for WEC080C2X030

Page 1: ...es without notice and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE whl 035 Rev 002 Rel 002 Date 11 1 17 The surface...

Page 2: ...on of the National Electrical Code NFPA No 70 Part 1 General Safety Information This water heater is approved for indoor installations only and is not intended for use as a pool heater Clearance to co...

Page 3: ...e of any fire rated assembly UNCRATING THE WATER HEATER Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee Installer Read all i...

Page 4: ...ting system and put safe operation at risk Ensure that the installation location adheres to the information included in this manual Failure to do so could result in property damage serious personal in...

Page 5: ...other treatment solutions if water is being over softened below 5 grains gallon 85 mg L Chloride concentration less than 100 ppm mg L Do not fill appliance or operate with water containing chlorides...

Page 6: ...69 23 1 4 8 UL 1453 3 4 NPT 151 120oF 48 8 C 181oF 82 8 C 200oF 93 3 C WEC100 100 7 1 4 52 61 27 206 WEC115 115 60 1 4 69 224 Table 2 Specifications and Dimensions Refers to Electrical Specifications...

Page 7: ...n Figure 3 for the electric water heater to operate properly Failure to install these fittings properly will result in improper water heater operation possible substantial property damage and increase...

Page 8: ...the water heater and check valve and must be sized for the entire water volume of the hot water system See piping Applications Other methods of controlling thermal expansion are available Check with t...

Page 9: ...URE TO RE INSPECT THE T P VALVE AS DIRECTED COULD RESULT IN UNSAFE TEMPERATURE AND OR PRESSURE BUILD UP WHICH CAN RESULT IN PROPERTY DAMAGE SERIOUS PERSONAL INJURY OR DEATH Do not thread a cap or plug...

Page 10: ...perage requirements The voltage requirement and dedicated wattage load for the heater is specified on the rating label of the water heater Consult your local power company to determine if your electri...

Page 11: ...Heating elements will be damaged if energized for even a short time while tank is dry Failures due to dry firing ARE NOT covered by warranty A Combination Thermostat and High Limit Control ECO After...

Page 12: ...mpting heating element replacement will result in property damage severe personal injury or death due to electric shock STEP 2 Run hot water at a faucet in the system When it runs cold shut off the fa...

Page 13: ...ter faucet s once all air has been bled from the system when water runs freely Make certain that the heater is completely full of water before restoring power Periodically At least twice a year Check...

Page 14: ...disposal Replacement of the valve is required if no water flows when the lever is operated Turn the water heater off until the valve is replaced If water flows from the valve drain a few gallons from...

Page 15: ...thermostat setting or replace 3 Tighten wire connections Improper wiring Check and rewire per Wiring Detail Not Enough Hot Water Heater undersized Reduce rate of heater use Defective element s Check a...

Page 16: ...copy of the original sales receipt or the warranty registration the warranty period for the water heater shall then be deemed to have commenced on the date of manufacture of the water heater and NOT t...

Page 17: ...opy of the original sales receipt You must present a copy of the original sales receipt for a warranty service request If your water heater is in warranty contact the retailer from whom the water heat...

Page 18: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Reviews: