background image

TYPE  KA  CARRIER  AUXILIARY  RELAY 

183A435 

Fig.  2.  Internal  Schematic  of  the  Type 

KA 

Relay  in  Type 

FT  32  Case. 

on the  operating 

cr. 

The  primary  of  the  transformer  is  tapped  and 

brought  out  to  a  tap  connector  block  for  ease  in 

changing  the  pick-up  current  of  the  relay.  The  use  of 
a  tapped  transformer  provides  approximately  the  same 
energy  level  at  a  given  multiple  of  pick-up  current 
for  any  tap  setting,  resulting  in  one  time  curve 
throughout  the  range  of  the  relay. 

Across  the  secondary  is  connected  a  non-linear 

resistor  known 

as 

a  varistor. 

The  effect  of  the 

varistor  is  to  reduce  the  voltage  peaks  applied  to  the 

overcurrent  unit  and  phase  shifting  capacitor. 

� 

irectional  Auxiliary  Units 

These  are  tw'o  solenoid-type  contactor  switches 

designated  as  CSP  and  CSG. 

The  phmger  of  the 

contactor  switch  has  a  circular  conducting  disc 

mounted  on  its  lower  end  and  as  the  plunger  travels 

upward,  the  disc  bridges  three  silver  stationary  con­

tacts.  The  CSP  switch  is  energized  by  the  operation 
of  the  second  zone  unit  of  the  KD  distance  relay, 
and  the  CSG  switch,  by  the  operation  of  the  direction­

al 

and  overcurrent  units  of  the  ground  relay.  The 

contacts  of  the  two  switches  are  connected  in parallel 
as  shown  in  the  internal  schematic.  The  operation  of 

40 

36 

:: 

32 

-

� 

28 

"' 

::: 

ii 

24 

!!! 

... 

20 

-

;::: 

� 

15 

ii 

� 

C> 

12 

-

-c 

:;;; 

C> 

10 

12 

14 

II 

18 

20 

MULTIPLES 

or 

PICKUP  CURREIT 

or 

CARRIER- START  OYERCURREIT 

um 

Curve 

471o61 

Fig.  3.  Typical  Time  Characteristics  of  carrier  start  over­

current  unit  of  the  type 

KA 

Relay. 

either  of  these  switches  connects  the  carrier  control 
circuit  to  negative 

to 

stop  carrier,  and  energizes  the 

RRT  operating  coil  of  the  receiver  relay  unit. 

Receiver  Uni t 

The  polarized  relay  consists  of  an  armature  and 

contacts  mounted  on  a  leaf  spring  supported  sym­
metrically  within  a  magnet  frame.  The  armature  rides 
in  the  front  air  gap  of  the  frame  with  the  contacts 
projecting  outside.  The  poles  of  a  permanent  magnet 

clamp  directly  to  each  side  of  the  frame.  Two  ad­

justable  shunts  are  located  across  the  rear  air  gaps. 

These  change  the  reluctance  of  the  magnetic  path  as 
shown  in  Fig. 

so  as  to  force  some  of  the  flux  thru 

the  moving  armature  which  is  fastened  to  the  frame 
midway  between  the  two  rear 

air 

gaps.  Flux  in  the 

armature  polarizes  it  and  creates  a  magnetic  bias, 

causing  it  to  move  towards  either  the  left  or  right, 

depending upon the  adjustment. 

Two  stationary  contact  screws  are  mounted  to  the 

left  (front  view)  of  the  moving  contact  assembly  and 
adjusted  for  normally  open  contacts. 

These  con­

tacts are  designated, RRP  and  RRG, and  are  connected 
in  the  phase  and  ground  trip  circuits  respectively. 

These  contacts  are  operated  by  two  concentric  coils, 

RRT  and  RRH,  which  are  placed  around  the  armature 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for 41-923.2

Page 1: ...agnetic core which houses NEW INFORMATION the lower pin bearing is secured to the frame by a locking nut The bearing can be replaced if neces sary without having to remove the magnetic core from the f...

Page 2: ...1 OVERCURRENT UNIT TAP BLOCK RRP CONTACT RRG CONTACT POLAR UNIT ALARM RELAY Al CARRIER START CONTACT los CARRIER START OVERCURRENT UNIT los SPARE TAP SCREW POLAR UNIT RECEIVER RELAY CSP AUXILIARY SWIT...

Page 3: ...36 32 28 ii 24 20 15 ii C 12 u c C u 0 0 10 12 14 II 18 20 MULTIPLES or PICKUP CURREIT or CARRIER START OYERCURREIT um Curve 471o61 Fig 3 Typical Time Characteristics of carrier start over current un...

Page 4: ...zed by a single coil and operates a single set of contacts The coil is energized by the received carrier to close the contacts and give an alarm This element has a higher pick up than that of the rece...

Page 5: ...nuts on the stud and then turning the proper nut with a wrench The carrier relaying schematic supplied with the carrier order should be consulted for details of the external connections of these relay...

Page 6: ...spring is adjusted by placing 6 a screwdriver or similar tool into one of the notches located on the periphery of the spring adjuster and rotating it The spring adjuster is located on the underside o...

Page 7: ...screw affect the adjustment on the other shunt screw Polar Alarm Unit The contacts should close with 8 milliamperes d e 5 applied to the alarm coil Adjust the contact screws to obtain an 050 contact...

Page 8: ...p Value Current Angle at 5 amperes Angle 5 37 3 9 24 4ff 75 38 36 13 37 5 2 1 39 35 8 5 34 1 25 41 34 6 0 32 1 5 43 32 4 6 31 2 45 30 2 9 28 1 41 36 9 0 36 1 5 44 32 5 0 32 1 4 2 47 30 3 0 29 2 5 50 2...

Page 9: ...L USE 2 18 STUD 16 190 3ZSCREW FOR THICK PANEL USii 190 32 STUD TERMINAL ND 1 0U NTING DETAILS NOTE ALL DIMEN 01 1 It INCHE TERMII lAL PANEL CUtOUT DRILLIN q FOR SEMI FLVSH MTG P NEL DRILL NC OR C UTO...

Page 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 11: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 12: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY DEPARTMENT NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 13: ...ch houses SUPERSEDES I L 41 923 2 Denotes change from superseded issue the lower pin bearing is secured to the frame by a locking nut The bearing can be replaced if neces sary without having to remove...

Page 14: ...ERCURRENT UNIT TAP BLOCK RRP CONTACT RRG CONTACT POLAR UNIT ALARM RELAY AL CARRIER START CONTACT los CARRIER START OVERCURRENT UNIT los SPARE TAP SCREW POLAR UNIT RECEIVER RELAY CSP AUXILIARY SWITCH F...

Page 15: ...chematic The operation of 40 36 32 28 3 iii 24 20 16 ii 12 4 0 0 10 12 14 18 18 20 MULTIPLES OF PICKUP CURREIT OF CARRIER START OYERCURREIT URIT Curve 47lo61 Fig 3 Typical Time Characteristics of carr...

Page 16: ...cator The operation indicator gives a visual indication of a carrier tripping operation for phase faults by the distance relay through the RRP contacts For a ground fault carrier relaying operation th...

Page 17: ...ts on the stud and then turning the proper nut with a wrench The carrier relaying schematic supplied with the carrier order should be consulted for details of the external connections of these relays...

Page 18: ...he spring is adjusted by placing 6 a screwdriver or similar tool into one of the notches located on the periphery of the spring adjuster and rotating it The spring adjuster is located on the underside...

Page 19: ...t screw affect the adjustment on the other shunt screw Polar Alarm Unit The contacts should close with 8 milliamperes d e 5 applied to the alarm coil Adjust the contact screws to obtain an 050 contact...

Page 20: ...p Value Current Angle at 5 amperes Angle 5 37 39 24 4ff 75 38 36 13 37 5 2 1 39 35 8 5 34 1 25 41 34 6 0 32 1 5 43 32 4 6 31 2 45 30 2 9 28 1 41 36 9 0 36 1 5 44 32 5 0 32 1 4 2 47 30 3 0 29 2 5 50 28...

Page 21: ...N t L USE 2 18 STUD 16 190 32 s c Rr w FOR THIC K PANEL US 190 32 STUD TERMINAL O ND MOU NTING DETPIIL5 NOTE A LL DIMENS OW i It t INC E Icc ll PANEL CUtOUT DRILLING FOR SEMI FLUSH Ml j f lo NE DRILL...

Page 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 24: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY DEPARTMENT NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: