background image

 

 

*AIR OR GAS 

 

Sales Manual Section 332 

PRODUCT SPECIFICATION PS 83939-E 

 

Lockout Relay 

83939-E1

 

 

B.     Mounting 

When installing the No. 83939-E 1 Lockout 

Relay, 

care should be taken to prevent any foreign matter 

from entering the ports. Provisions should be 

made to 

prevent foreign matter from entering the ports 

which are left open to the atmosphere. 

The relay may be installed in any position, but 

vertical (upright) is recommended. The relay 

should be 

securely mounted, using the two slots (clearance 

for No. 10 screws), provided in the mounting 

bracket (See Figure 1). 

J. I. C. Symbol 

Form No. P-2317 (Rev. B) 

GENERAL DESCRIPTION

 

 

The No. 83939-E1 Lockout Relay is a two-way, 

diaphragm-actuated, non-venting, normally open 
valve. It is used in the safety system to lock out or 
block certain portions of the control system or a line in 
a control system upon receipt of a signal at PORT 1. 
(See Figure 1). It will reopen with the loss of pressure 
at PORT 1, and has a connection which may be used to 
cancel the actuating pressure at PORT 1. 
 
 
 

SPECIFICATIONS 

Construction: 

Aluminum body; stainless steel cover, 

bracket and springs; elastomer coated fabric 
diaphragms and gaskets; stainless steel and 
aluminum valve with resilient seat. 

Supply Pressure: 

...........................................

See Figure 2. 

CAUTION: DO NOT EXCEED MAXIMUM PRESSURES 

Maximum Pressure: 

......................................

See Figure 2. 

Mounting: 

.................................................................

Surface 

Dimensions: 

...................................................

See Figure 1. 

Connections: 

................................................

1/8"-27 NPT. 

Approximate Shipping Weight: 

.............

12 ozs. (.340 kg)  

Ordering Information: 

Specify: No. 
83939-E1 

 
 
 

INSTALLATION 

A.     General 

Tubing and fittings used to connect the relay 

must be free of chips, dirt, and moisture or other 
foreign material. 

It is recommended that an "anti-seize" type 

thread compound be applied to the second or third 
male thread in moderate amount. Do not allow 
compound to be deposited inside the relay. Thread 
sealing tape is not recommended. 

For continuous, trouble-free operation, the 

supply to the relay must be clean and dry. 

 

Summary of Contents for 83939-E1

Page 1: ...of a signal at PORT 1 See Figure 1 It will reopen with the loss of pressure at PORT 1 and has a connection which may be used to cancel the actuating pressure at PORT 1 SPECIFICATIONS Construction Aluminum body stainless steel cover bracket and springs elastomer coated fabric diaphragms and gaskets stainless steel and aluminum valve with resilient seat Supply Pressure See Figure 2 CAUTION DO NOT EX...

Page 2: ...t off seat opening Port 3 again to Port 2 Also the relay may be reopened by applying an equalizing pressure through Port 4 NOTE Graph A indicates actuating pressure Port 1 required to keep valve closed at various supply pressures Port 3 Also Graph A indicates actuating pressure Port 1 minus equalizing pressure Port 4 required to keep valve closed at various supply pressures Port 3 NOTE Graph B ind...

Page 3: ...ssembly check for external leakage Retighten assembly screws as necessary Gasket cement should not be used to seal leaks due to the possibility of plugging small passages or damaging the operating characteristics of the diaphragms CAUTION If cleaning is required do not subject O rings valve poppets diaphragms or gaskets to cleaning fluid acetone or any halogenated hydrocarbons such as vapor degrea...

Page 4: ...ual and lubricant PARTS LIST DET NO NO REQ D DESCRIPTION DWG NO 1 4 Screw 33713 H2409 2 4 Lockwasher 36600 L0609 3 1 Mounting Bracket 24637 C2 4 1 Relay Body 31857 E1 5 1 Head Stem Assembly 85013 81 6 1 O Ring 36240 C10 7 1 Plug Guide Assembly 99264 B1 8 1 Nameplate 30036 G2 9 1 Relay Body 31857 D1 10 1 Spring 25121 A1 11 2 Gasket 33665 B 1 12 1 Spring 24598 A1 13 1 Diaphragm 24498 A1 14 1 Spacer ...