background image

TYPE  AR  RELAY 

.3 

the 

0.1. 

This  value  of  current  should  be  not 

greater  than  the  particular 

0.1. 

tap  setting  being 

used.  The  operation  indicator  target  should  drop 

freely. 

6.  Indicating  Contactor  Switch  (ICS)  (When  Supplied) 

Close  the  main  relay  contacts  and  pass  sufficient 

de  current  through  the  trip  circuit  to  close  the 

contacts  of  the  ICS.  This  value  of  current  should 

be  not  greater  than  the  particular  ICS  tap  setting 

being  used.  The  operation  indicator  target  should 

drop  freely. 

The  contact  gap  should  be  approximately  .047" 

between  the  bridging  moving  contact  and  the 

stationary  contacts.  The  bridging  moving  contact 

should  touch 

the  stationary  contacts  simulta­

neously. 

CALIBRA TION 

Use  the  following  procedure  for  calibrating  the 

relay  if  the  relay  has  been  taken  apart  for  repairs  of 

the  adjustments  disturbed.  This  procedure  should 

not  be  used  until  it  is  apparent  that  the  relay  is  not 

in  proper  working  order.  (See  "Acceptance  Check.") 

Tripping  Relay  (AR) 

The  type AR  tripping  relay  unit  has  been  properly 

adjusted  at  the  factory  to  insure  correct  operation, 

and  under  normal  field  conditions  should  not  require 

readjustment.  If,  however,  the  adjustments  are  dis­

turbed  in  error,  or  it  becomes  necessary  to  replace 

some  part,  use  the  following  adjustment  procedure. 

This  procedure  should  not  be  used  until  it  is 

apparent  that  the  relay is  not  in  proper  working order. 

a.  Adjust  the  set  screw  at  the  rear  of  the  top  of  the 

frame  to  obtain  a  0.010-inch  gap  at  the  rear  end 
of  the  armature  air  gap. 

b.  Adjust  each  contact  spring  to  obtain  5  grams 

pressure  at  the  very  end  of  the  spring.  This  pres­

sure  should  be  sufficient  to  move  the  spring 

away from  the  edge  of  the  slot  of  the  card. 

c.  Adjust  each  stationary  contact  screw  to  obtain  a 

contact  gap  of  0.020  to  0.022  inches  for  the  nor­

mally  open  contacts.  Energize  the  relay  and  the 

normally  open  contacts  should  have  15  to  30 

grams  contact  follow. 

d.  Apply  rated  voltage  to  the  relay  in  line  with  the 

terminal  polarity  designation.  Then  calibrate  by 

adjusting  the  spring  tension  until  the  relay  picks 
up  in  line  with  TABLE  III. 

TABLE  III 

31  volts  for  48  volt  rating 

80  volts  for  125  volt  rating 

160  volts  for  25 0  volt  rating 

RE NE WAL  P AR T S  

Repair  work  can  be  done  most  satisfactorily  at 

the  factory.  However,  interchangeable  parts  can  be 

furnished  to  the  customers  who  are  equipped  for 

doing  repair  work.  When  ordering  parts,  always  give 
the  complete  name plate  data. 

TABLE  IV 

CONTACT INTERRUPTING CAPABILITY (AMPERES) 

RESISTIVE LOAD 

INDUCTIVE  LOAD 

D.C.  VOLTAGE 

WILL  INTERRUPT 

WILL  INTERRUPT 

250 

0.2 

0.1 

125 

0.5 

0.25 

48 

1.5 

1.0 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for 41-759.3

Page 1: ...ted to the laminations The card moves with the armature thereby operating the moving contacts The tension of the moving contacts is the resetting force S U PERSED ES L914464 Complete Revision High spe...

Page 2: ...LATION BLOCK 2 NORMALLY OPEN STATIONARY CONTACT SCREWS 3 LEAF SPRING MOVING CONTACTS 4 MOVING CARD ASSEMBLY 5 RELAY COIL Fig 1 Type AR Unit with four make contacts front view w w w E l e c t r i c a l...

Page 3: ...LY OPEN STATIONARY CONTACT SCREWS 3 MOVING ARMATURE 4 U SHAPED LAMINATED CORE 5 ARMATURE GAP ADJUSTMENT SET SCREW Fig 2 Type AR Unit with four make contacts side view 3 w w w E l e c t r i c a l P a r...

Page 4: ...means of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projec tion mounting Either a mounting stud or the mounting screws may be uti...

Page 5: ...in error or it becomes necessary to replace some part use the following adjustment procedure This procedure should not be used until it is apparent that the relay is not in proper working order a Adj...

Page 6: ...case 6 RIGHT CENTER l F V I RIGHT HAND lf V HINGED ARMATURE UNIT REAR VIEW LEFT CENTER l f V LEFT HANO l f V I 1001l 48 V D C 15001t 115 V D C 6000Jl 150 V D C 3 512A30 Fig 4 Internal schematic of th...

Page 7: ...RED HANDLE TEST SWITCH TERMINAL 3512A73 Fig 7 Internal schematic of the Type AR Relay High Threshold double unit with 8 make contacts in FT 2 2 case Fig B Internal schematic of the Type AR Relay High...

Page 8: ...E HOLE FOR 190 SCREW N TERhiiNAL 190 TERMINAL HARDWARE r 4 _1_ I 64 4 Fig 10 Outline and drilling plan for the Type AR relayin the front connected molded case 8 836A991 w w w E l e c t r i c a l P a r...

Page 9: ...TYPE AR RELAY L 4 1 7 5 9 3 182A904 Fig 11 Outline and drilling Plan for the Type AR Relay in the rear connected molded case 9 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 10: ...MOLES FO 190 32 MTG SC EWS PAIIEL CUTOUT DIULLIMG FOR SEMI FLUSH MTG B 2 __ ___ f ool l 16 33 __ 1 611 i I I 1 1 1l 32 32 32 32 PANEL DI ILLIMG OR CUTOUT FOR PROJECTION MTG FRONT VIEW 9 f6 DIA HOLE 3...

Page 11: ...UIALI AID MOUITII DETAILS 2 5 2 32 r 5 DIA II HOLES FO 190 32 MTG SCREWS _ Cll t 1 1_ 2 J rJ 18 7 5B PAIIEL CDTOUT I Oil LLIMG FORtSEMI FLUSH MTG PAIIEL OIIUIMG DR CUlOUT FOR PROJECTIOII MTG FROIIT Yl...

Page 12: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISI0N NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: