Leonardo Off-Grid 1kW/1500/24
User Manual
EN
17
ELECTRICAL FEATURES
Leonardo Off-Grid
1kW / 1500/24 GE
Leonardo Off-Grid
4kW / 3000/48 GE
Leonardo Off-Grid
4kW / 5000/48 GE
Leonardo Off-Grid
8kW / 8000/48 GE
IN
VE
R
TE
R
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Output power
Pout
-
1,500VA 3,000W
-
3,000VA 6,000W
-
5,000VA 10,000W
-
8,000VA 16,000W
Battery Voltage
Vbatt
20.0V
24V
33V
40.0V
48V
66V
40.0V
48V
66V
40.0V
48V
66V
Output voltage
Vac
-
230V
-
-
230V
-
-
230V
-
-
230V
-
Output frequency
Fac
-
50Hz
± 0.1%
-
-
50Hz
± 0.1%
-
-
50Hz
± 0.1%
-
-
50Hz
± 0.1%
-
Transfer time Inverter <>
Bypass
Tsw
-
10mS
-
-
10mS
-
-
10mS
-
-
10mS
-
Overload threshold
Poc
-
85%
-
-
85%
-
-
85%
-
-
85%
-
Efficiency
Eff
-
94%
-
-
95%
-
-
95%
-
-
95%
-
Absorption in bypass
Pbp
-
<4W
-
-
<5W
-
-
<6W
-
-
<6W
-
Self-consumption in
stand-by mode
Psb
-
10W
-
-
16W
-
-
25W
-
-
25W
-
Switching threshold
Inverter Mode / Bypass
Mode
Tba
22.9V
23.0V
23.1V
45.9V
46.0V
46.1V
45.9V
46.0V
46.1V
45.9V
46.0V
46.1V
Switching threshold
Bypass Mode / Inverter
Mode
Tbs
27.1V
27.2V
27.3V
54.3V
54.4V
54.5V
54.3V
54.4V
54.5V
54.3V
54.4V
54.5V
Internal over-
temperature alarm
Tot
65°C
65°C
65°C
65°C
Operating temperature
Tamb
-10°C
25°C
60°C
-10°C
40°C
60°C
-10°C
25°C
60°C
-10°C
25°C
60°C
PV CH
A
R
GE
R
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Battery Voltage
Vbatt
-
24.0V
-
-
48.0V
-
-
48.0V
-
-
48.0V
-
MPPT Inputs
Nmpp
-
2
-
-
4
-
-
4
-
-
4
-
Module current per
channel
Ipan
-
-
13.0A
-
-
13.0A
-
-
13.0A
-
-
26.0A
Open circuit module
voltage
Vpan
-
-
200V
-
-
200V
-
-
200V
-
-
200V
Maximum power per
channel
Pch
-
560W
-
-
1.15kW
-
-
1.15kW
-
-
2.20kW
-
Total maximum power
Pmax
-
-
1.15kW
-
-
4.6kW
-
-
4.6kW
-
-
9.00kW
Charging voltage at 25° C
(ABSORPTION)
VEoC
-
28.8V
-
-
57.6V
-
-
57.6V
-
-
57.6V
-
ABSORPTION phase time
Tabs
-
4h
-
-
4h
-
-
4h
-
-
4h
-
Rest voltage
(FLOAT)
Vflt
-
27.6V
-
-
55.2V
-
-
55.2V
-
-
55.2V
-
Efficiency
Eff
-
97.2%
-
-
97.2%
-
-
97.2%
-
-
97.2%
-
VEoC function
compensation of battery
temperature (Tbatt)
Vtadj
-
-96
mV/°C
-
-
-96
mV/°C
-
-
-96m
V/°C
-
-
-96
mV/°C
-
Self-consumption
Iq
-
12 mA
-
-
12 mA
-
-
12 mA
-
-
12 mA
-
Operating temperature
Tamb
-10°C
25°C
60°C
-10°C
25°C
60°C
-10°C
25°C
60°C
-10°C
25°C
60°C
Power dissipation
Pdiss
66W
66W
66W
66W
E
N
CLO
S
URE
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Min
Typ
Max
Section of battery cables
-
25mm²
-
-
25mm²
-
-
35mm²
-
-
50mm²
-
Lenght of battery cables
-
1.5mt
-
-
1.5mt
-
-
1.5mt
-
-
1.5mt
-
Protection degree
IP20
IP20
IP20
IP20
Dimensions
315x750x130 mm
395x940x250 mm
395x940x250 mm
395x940x300 mm
Weight
14 Kg
25 Kg
37 Kg
55 Kg
Tab.5 Electrical features
Summary of Contents for 014392
Page 1: ...Leonardo Off Grid 1kW 1500 24 GE Manuale utente User manual IT EN ...
Page 2: ......
Page 40: ......