RT-370 User Guide
Page 25 (34)
4.7 Connecting the AC Power Feed
The power feed is connected to the AC power feed connector.
NOTICE
: The installation of the AC power must be done by trained professionals. It must be ensured that there is
no power applied to the AC wires during the installation work.
The Protective Earth must be connected before connecting the power feeds.
NOTICE
: When installing the product, it must be ensured that direct access to the AC plug is always possible and
that the user is able to disconnect the AC plug to remove power from the device.
Figure 15 AC interface
Pin
Signal Name, Function
Notes
1
AC Phase
Connector Type: Binder 693 male socket 3+PE
2
AC Neutral
3
-
4
Protective Earth
Table 18 Pinning: AC Mains Connector
Order of Installation Step
Description
1. Assembly of Binder connector
Assemble cable connector according pin out given above.
Use ferrules and follow instructions of system integrator for reliable
operation.
2. Install the cable
Install cable to the AC plug
Use appr. 1.0 Nm tightening torque.
Table 19 Installation Procedure, Installing AC Cable