11

6621-2260

Diagnostic

QoS indication

The QoS indication on the front of the unit gives an indication of the pilot wire link sta-
tus.  
If indication shows weak link it is recommended to improve the pilot wire characteristic.  
A weak link can be unstable and result in data transmission losses.

RPW-diagnostic tool connection

The RPW-diagnostic tool, which is part of the RPW-
diagnostic kit, can be used for more advanced diagnostic 
and logging of diagnostic parameters. Connection to the 
RPW-unit is possible via the  
console port in the front of the unit using the serial con-
sole cable, also part of the diagnostic kit.
The following steps needs to be taken
1.  Connect the serial diagnostic cable to the console port. 
(Use only the cable provided in Diagnostic Kit).
2.  Connect cable to your computer  
(USB port, if drivers are needed they can be found on the CD in the RPW-diagnostic kit).
3.  From RPW-diagnostic tool connect to the assigned port.

RPW-diagnostic tool

The RPW-diagnostic tool has a built in help. Set the pointer over a specific item and 
information about that part will pop-up automatically.

Summary of Contents for Pilot Wire RPW600F

Page 1: ...Pilotwire modem RPW600M RPW600F User Guide 6621 2260...

Page 2: ...of merchantability and fitness for a particular purpose are made in relation to the accuracy and reliability or contents of this document The manufacturer reserves the right to revise this document o...

Page 3: ...us voltage may occur within this unit when connected to power supply Care recommendations Follow the care recommendations below to maintain full operation of unit and to fulfil the warranty obligation...

Page 4: ...The fibre optic cable must also be handled the same way If this recommendation not will be followed it can jeopardise the warranty Cleaning of the optical connectors In the event of contamination the...

Page 5: ...o enable ease of use no setting or configuration is needed with either of the RPW600 modem variants Pilot wire link lengths typically up to 8 km with 0 8 mm2 twisted pair cables can be applied With tw...

Page 6: ...ted EN 61000 4 3 20V m 80 2700 MHz Performance Criteria A Electrical fast transient Burst EN 61000 4 4 4 0 kV power ports 4 0kV signal ports Performance Criteria A Surge EN 61000 4 5 4 0 kV L E power...

Page 7: ...6 Test Fc 10 150 Hz 0 075 mm 10 58 Hz 10m s 58 150 Hz 1 sweep cycles in each of the three directions Vibration endurance test IEC 60068 2 6 Test Fc 10 150 Hz 20m s 58 150 Hz 20 sweep cycles in each o...

Page 8: ...Not required External supply current capability for proper startup Pilot Wire Isolation to All other Connection Detachable screw terminal Connector size 0 2 2 5 mm AWG 24 12 Shielded cable Not requir...

Page 9: ...tions Pilot wire Position Direction Description 1 In Out 2 wire Receive Transmit 2 In Out 2 wire Receive Transmit Direction relative this unit Console see more information on page 8 LED indicators see...

Page 10: ...a is transmitted PW Pilot wire link indication OFF Inactive link GREEN Active link GREEN FLASH Link negotiation QoS Quality of service pilot wire link quality indication LED 1 LED 2 LED 3 1 2 3 GREEN...

Page 11: ...agnostic parameters Connection to the RPW unit is possible via the console port in the front of the unit using the serial con sole cable also part of the diagnostic kit The following steps needs to be...

Page 12: ...Removal Press down the support at the back of the unit using a screwdriver See figure Cooling This unit uses convection cooling To avoid obstructing the airflow around the unit use the following spaci...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...REV A 6621 2260 2010 07 Made for ABB by Westermo Teleindustri AB ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094...

Reviews: