![Westermo Pilot Wire RPW600F User Manual Download Page 7](http://html1.mh-extra.com/html/westermo/pilot-wire-rpw600f/pilot-wire-rpw600f_user-manual_960417007.webp)
7
6621-2260
Type tests emission
Environmental
phenomena
Basic
Standard
Environment
Radiated emission
Enclosure
30 MHz – 230 MHz
230 MHz – 1000 MHz
EN 55022
Class A
EN 55022
Conducted emission
DC power port
0.15 – 30 MHz
EN 55022
Class A
EN 55022
Type tests temperature
Environmental
Phenomena
Standard
Test values
Cold test
IEC 60068-2-1
Test Ad
–25ºC; 96 h
–40ºC; 16 h
Dry heat test
IEC 60068-2-2
Test Bd
+55ºC; 96 h
+85ºC; 16 h
Damped heat test, cyclic
IEC 60068-2-30
6 cycles, 12+12 h
+25ºC ... +55ºC
Storage test
IEC 60068-2-48
–40ºC; 96 h
+85ºC; 96 h
Type tests mechanical
Environmental
Phenomena
Standard
Test values
Vibration response test
IEC 60068-2-6
Test Fc
10 – 150 Hz
0.075 mm, 10 – 58 Hz
10m/s², 58 – 150 Hz
1 sweep cycles in each of the three directions
Vibration endurance test
IEC 60068-2-6
Test Fc
10 – 150 Hz
20m/s², 58 – 150 Hz
20 sweep cycles in each of the three directions
Shock response test
IEC 60068-2-27
Test Ea
Peak acc: 100 m/s²
Duration: 11 ms
3 pulses in each of the six directions
Shock withstand test
IEC 60068-2-27
Test Ea
Peak acc: 300 m/s²
Duration: 11 ms
3 pulses in each of the six directions
Bump test
IEC 60068-2-29
Test Eb
Peak acc: 200 m/s²
Duration: 16 ms
1000 pulses in each of the six directions
Type tests insulation
Test
Standard
Test values
Dielectric test
EN 60255-5
5 kVac, Pilot Wire – Power
5 kVac, Pilot Wire – GND
2 kVac, Power – GND
Impulse voltageTest
EN 60255-5
5 kV
Isolation resistance test
EN 60255-5
0.5 kV, >100M
Ω
Protective bonding resistance
EN 60255-27
<0.1
Ω
(60 s)