![Westermo Pilot Wire RPW600F User Manual Download Page 8](http://html1.mh-extra.com/html/westermo/pilot-wire-rpw600f/pilot-wire-rpw600f_user-manual_960417008.webp)
8
6621-2260
Interface specifications
Power
Rated voltage
24 to 110 VDC
Operating voltage
19,2 to 154 VDC
Rated current
200 mA @ 24 VDC
50 mA @ 110 VDC
Rated frequency
DC
Inrush current, I2t
0.11 A²s @ 48 VDC
Startup current*
0.2 Apeak @ 24VDC
Polarity
Reverse polarity protected
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm² (AWG 24 – 12)
Shielded cable
Not required
* External supply current capability for proper startup.
Pilot Wire
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm² (AWG 24 – 12)
Shielded cable
Not required
Number of ports
1
Ethernet FX
Isolation to
All other
Connection
LC
Fibre type
Single-mode 9/125 or 10/125
Shielded cable
Not required
Number of ports
1
Console
Electrical specification
TTL-level
Data rate
115.2 kbit/s
Data format
8 data bits, none parity, 1 stop bit, no flow control
Transmission range
15 m
Isolation to
All other
Connection
2.5 mm jack, use serial console cable