8

6621-2260

Interface specifications

Power 

Rated voltage

24 to 110 VDC

Operating voltage

19,2 to 154 VDC

Rated current

200 mA @ 24 VDC 
  50 mA @ 110 VDC 

Rated frequency

DC

Inrush current, I2t

0.11 A²s @ 48 VDC

Startup current*

0.2 Apeak @ 24VDC

Polarity

Reverse polarity protected

Isolation to

All other

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

Shielded cable

Not required

*  External supply current capability for proper startup.

Pilot Wire

Isolation to

All other

Connection

Detachable screw terminal

Connector size

0.2 – 2.5 mm² (AWG 24 – 12)

Shielded cable

Not required 

Number of ports

1

Ethernet FX

Isolation to

All other

Connection

LC

Fibre type

Single-mode 9/125 or 10/125

Shielded cable

Not required 

Number of ports

1

Console

Electrical specification

TTL-level

Data rate

115.2 kbit/s

Data format

8 data bits, none parity, 1 stop bit, no flow control

Transmission range

15 m

Isolation to

All other

Connection

2.5 mm jack, use serial console cable

Summary of Contents for Pilot Wire RPW600F

Page 1: ...Pilotwire modem RPW600M RPW600F User Guide 6621 2260...

Page 2: ...of merchantability and fitness for a particular purpose are made in relation to the accuracy and reliability or contents of this document The manufacturer reserves the right to revise this document o...

Page 3: ...us voltage may occur within this unit when connected to power supply Care recommendations Follow the care recommendations below to maintain full operation of unit and to fulfil the warranty obligation...

Page 4: ...The fibre optic cable must also be handled the same way If this recommendation not will be followed it can jeopardise the warranty Cleaning of the optical connectors In the event of contamination the...

Page 5: ...o enable ease of use no setting or configuration is needed with either of the RPW600 modem variants Pilot wire link lengths typically up to 8 km with 0 8 mm2 twisted pair cables can be applied With tw...

Page 6: ...ted EN 61000 4 3 20V m 80 2700 MHz Performance Criteria A Electrical fast transient Burst EN 61000 4 4 4 0 kV power ports 4 0kV signal ports Performance Criteria A Surge EN 61000 4 5 4 0 kV L E power...

Page 7: ...6 Test Fc 10 150 Hz 0 075 mm 10 58 Hz 10m s 58 150 Hz 1 sweep cycles in each of the three directions Vibration endurance test IEC 60068 2 6 Test Fc 10 150 Hz 20m s 58 150 Hz 20 sweep cycles in each o...

Page 8: ...Not required External supply current capability for proper startup Pilot Wire Isolation to All other Connection Detachable screw terminal Connector size 0 2 2 5 mm AWG 24 12 Shielded cable Not requir...

Page 9: ...tions Pilot wire Position Direction Description 1 In Out 2 wire Receive Transmit 2 In Out 2 wire Receive Transmit Direction relative this unit Console see more information on page 8 LED indicators see...

Page 10: ...a is transmitted PW Pilot wire link indication OFF Inactive link GREEN Active link GREEN FLASH Link negotiation QoS Quality of service pilot wire link quality indication LED 1 LED 2 LED 3 1 2 3 GREEN...

Page 11: ...agnostic parameters Connection to the RPW unit is possible via the console port in the front of the unit using the serial con sole cable also part of the diagnostic kit The following steps needs to be...

Page 12: ...Removal Press down the support at the back of the unit using a screwdriver See figure Cooling This unit uses convection cooling To avoid obstructing the airflow around the unit use the following spaci...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...REV A 6621 2260 2010 07 Made for ABB by Westermo Teleindustri AB ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094...

Reviews: