M508 p/n 2M-304456 Owners Manual WV
-2HG
MAINTENANCE SCHEDULES
1. 6-MONTH MAINTENANCE (MUST BE PERFORMED BY AN
AUTHORIZED ANSUL® DISTRIBUTOR ONLY):
a.
Inspect and test total operation including FIRE DAMPER and
all SAFETY INTERLOCKS.
b.
All FIRE SUPPRESSION SYSTEM actuation components
including MANUAL PULL STATION and any REMOTE MANUAL
PULL STATION must be inspected for proper operation in
accordance with the maintenance schedule published in ANSUL®
R-102 SYSTEM DESIGN, INSTALLATION, RECHARGE AND
MAINTENANCE MANUAL (Ansul® #418087-05).
c.
The FIRE SUPPRESSION SYSTEM FUSIBLE LINKS must be
inspected. NOZZLES and MANUAL PULL STATION must be
cleaned in accordance with ANSUL® R-102 SYSTEM DESIGN,
INSTALLATION, RECHARGE AND MAINTENANCE MANUAL
(Ansul® #418087-05).
d.
The FIRE SUPPRESSION AGENT TANK, PIPING and FLEXIBLE
TUBING must be Inspected.
2. 12-YEAR MAINTENANCE: (MUST BE PERFORMED BY AN
AUTHORIZED ANSUL® DISTRIBUTOR ONLY):
a. The FIRE SUPPRESSION AGENT TANK and ¼” FLEX HOSE
must be hydrostatically tested, and the FIRE EXTINGUISHING
AGENT must be replaced in accordance with the maintenance
schedule published in ANSUL® R-102 SYSTEM (STANDARD UL
300 LISTED).
b.
The FUSIBLE LINKS in plenum and damper must be
REPLACED. This maintenance to be performed by qualified
Ansul® service personnel only.
USE AND MAINTENANCE
SHALL BE IN ACCORDANCE
WITH THE STANDARD FOR
VENTILATION CONTROL
AND FIRE PROTECTION OF
COMMERCIAL COOKING
OPERATIONS, N.F.P.A 17A &
N.F.P.A. 96
(current editions).
DANGER
Fire Hazard
FAILURE TO PROPERLY
CLEAN AND MAINTAIN THIS
EQUIPMENT CAN
CAUSE A FIRE. AN
UNCONTROLLED FIRE CAN
CAUSE SERIOUS INJURY,
DEATH AND/OR PROPERTY
LOSS.
NOTE: A signed and dated
VENTILATOR HOOD
MAINTENANCE LOG must be
maintained on the premises,
and shall be available for
inspection by the authority
having jurisdiction. See pages
25 & 26.
IMPORTANT: Parts used for
the Ansul® fire suppression
system are not serviceable
by the owner / operator.
Procedures for servicing fire
suppression equipment are
described in:
ANSUL® R-102 SYSTEM
DESIGN, INSTALLATION,
RECHARGE AND
MAINTENANCE MANUAL
(Ansul® #418087-05).
24