71
RF0300 Troubleshooting
SELF-CONTAINED AIR-COOLED
Normal Operation
When the toggle switch is placed in the “ON”
position the following controls must be in the
closed position before the ice machine will start:
A. Bin Thermostat
B. Low Evaporator Temperature Thermostat
C. Ice Chute Safety Switch
D. Low Water Level Switch
Placing the toggle switch in the ON position starts
the gear motor and a 10 minute compressor time
delay. The compressor starts and the float valve
controls the water inlet valve and water level.
The freeze cycle ends when ice contacts the bin
thermostat. The ice machine remains off until ice no
longer contacts the bin thermostat.
Summary of Contents for Manitowoc R
Page 1: ...Part Number 000007661 Rev01 05 17 R Model Flake Nugget Ice Machine Technician s Handbook...
Page 2: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 22: ...THIS PAGE INTENTIONALLY LEFT BLANK 22 Part Number 000007661 Rev01 05 17...
Page 220: ...THIS PAGE INTENTIONALLY LEFT BLANK 220 Part Number 000007661 Rev01 05 17...
Page 224: ...224 Part Number 000007661 Rev01 05 17 RF0300 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 252: ...252 Part Number 000007661 Rev01 05 17 RNS0308 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 260: ...260 Part Number 000007661 Rev01 05 17 RNS1000 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 270: ...270 Part Number 000007661 Rev01 05 17 RF1200 RFS1200 WATER COOLED 1 2 3 4 5 6 7 8...
Page 272: ...272 Part Number 000007661 Rev01 05 17 RF2300 RFS2300 AIR COOLED 1 2 3 4 5 6 7 8 8...
Page 274: ...274 Part Number 000007661 Rev01 05 17 RF2300 RFS2300 WATER COOLED 1 2 3 4 5 6 7 8 8...
Page 282: ...282 Part Number 000007661 Rev01 05 17 RN0400 RN1000 RN1400 AIR WATER COOLED 1 2 3 4 5 6...
Page 286: ...THIS PAGE INTENTIONALLY LEFT BLANK 286 Part Number 000007661 Rev01 05 17...
Page 287: ......