154
Part Number 000007661 Rev01 05/17
Hard Error
Gear motor amperage exceeds 3.8 amps a second time,
within six hours of the first failure. The ice machine must
be reset by pressing the control board reset button.
HI PRESSURE
Soft Error
If the refrigeration pressure exceeds 425 psi (2930 kPa)
the ice machine will turn off, energize the Hi Press light
and initiate a 60 minute delay period. If the refrigeration
pressure is below 295 psi (2034 kPa) at the end of the
delay period the ice machine will restart.
DRAIN CLOG
Soft error
When the drain sensor (located in the drain pan behind
the drain solenoid) detects water, the ice machine will
energize the Drain Clog light and turn off until reset.
Summary of Contents for Manitowoc R
Page 1: ...Part Number 000007661 Rev01 05 17 R Model Flake Nugget Ice Machine Technician s Handbook...
Page 2: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 22: ...THIS PAGE INTENTIONALLY LEFT BLANK 22 Part Number 000007661 Rev01 05 17...
Page 220: ...THIS PAGE INTENTIONALLY LEFT BLANK 220 Part Number 000007661 Rev01 05 17...
Page 224: ...224 Part Number 000007661 Rev01 05 17 RF0300 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 252: ...252 Part Number 000007661 Rev01 05 17 RNS0308 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 260: ...260 Part Number 000007661 Rev01 05 17 RNS1000 AIR COOLED Refer to Nameplate for Voltage Rating...
Page 270: ...270 Part Number 000007661 Rev01 05 17 RF1200 RFS1200 WATER COOLED 1 2 3 4 5 6 7 8...
Page 272: ...272 Part Number 000007661 Rev01 05 17 RF2300 RFS2300 AIR COOLED 1 2 3 4 5 6 7 8 8...
Page 274: ...274 Part Number 000007661 Rev01 05 17 RF2300 RFS2300 WATER COOLED 1 2 3 4 5 6 7 8 8...
Page 282: ...282 Part Number 000007661 Rev01 05 17 RN0400 RN1000 RN1400 AIR WATER COOLED 1 2 3 4 5 6...
Page 286: ...THIS PAGE INTENTIONALLY LEFT BLANK 286 Part Number 000007661 Rev01 05 17...
Page 287: ......