Use the following procedure and table to help determine
if a harvest valve is remaining partially open during the
freeze cycle.
1. Wait eight minutes into the freeze cycle.
2. Feel the inlet of the harvest valve or attach
thermocouple and insulate.
Ipprttat
Feeling the harvest valve outlet or across the harvest
valve itself will not work for this comparison.
The harvest valve outlet is on the suction side (cool
refrigerant). It may be cool enough to touch even if the
valve is leaking.
3. Feel the compressor discharge line.
n
Warning
The inlet of the harvest valve and the compressor
discharge line could be hot enough to burn your hand.
Just touch them momentarily.
4. Compare the temperature of the inlet of the harvest
valve to the temperature of the compressor discharge
line and refer to table.