18
G. Electric Power Supply
•
The electric supply must match all electrical and wiring requirements specified on the rating plate.
•
NOTE: This appliance is
NOT
Ground Fault Interrupter (GFI or GFCI) compatible.
•
NOTE: The 24CGP10 Electrical Diagram is located inside of the Condensate Drip Trough.
The connection must be made as follows:
1.
Install a main disconnect switch and a separate fuse or breaker for this appliance as shown in
Figure 3-9.
The fused disconnect switch is referred to as the “Main External Power Switch.”
2.
Do not use a GFI (GFCI) circuit. This appliance is not GFI compatible.
3.
Do NOT use a power cord.
4.
Make the electrical connection using flexible conduit, per local code. See Figure 3-10.
Figure 3-10
Hardwire Connection
Power 10
DRAIN LINE
COLD WATER SUPPLY LINES
MAIN EXTERNAL
POWER SWITCH
Figure 3-9
Electrical Layout
This appliance is not GFI (GFCI) compatible.
Do not use a GFI (GFCI) circuit.
Using a GFI (GFCI) circuit can result in injury, equipment damage, and property damage.