9.7 Check flue gas pressure switch
Observe notes on servicing (see Ch. 9).
▶
Switch on main switch.
▶
Set boiler to Standby (see Ch. 6.2.2). If a remote control station is fitted, see op-
erating instructions WCM-FS.
▶
Remove pressure measuring hose from test point
1
on the condensate collector.
▶
Check pressure measuring hose for damage.
▶
Connect test equipment
2
.
▶
Generate test pressure of > 5.5 mbar.
✓
The flue gas pressure switch functions correctly if the display shows
F38
.
▶
Reconnect pressure measuring hose.
▶
Reset system using [reset] button.
▶
Exit Standby mode.
Installation and operating instruction
Gas condensing boiler WTC-GB 90-A
9 Servicing
83266502 • 1/2010-08 • La
69-95